INSTALLER MENU SEQUENCE
BOILER MINIMUM RETURN
When a return sensor is connected to the SQ-Elite-8T, it will monitor and control the boiler
return when in Heating mode. It does that by monitoring the Target temperature (TGT),
System temperature (SYS), Minimum Return, and actual return. (RTN). When the SQ-Elite-8T
foresees that a low return will occur, it will increase the Target automatically as an effort to
increase the return temperature. See Return Sensor Wiring on page 14.
MINIMUM RETURN
Adjustable Off, from 80ºF/27ºC to 140ºF/60ºC
Default:
120ºF/49ºC
Hold Button:
MENU/Min. Return
in Heating only
•
The Minimum Return is the critical temperature at which the return should be above.
Normally, this setting is provided by the boiler manufacturer or the system engineer.
•
The SQ-Elite-8T will use that value as a guide. It will start to add additional stages if it
foresees that the RTN temperature will drop below the Min. Return. During that period,
it will display “
Hold Return at 120
o
F
” in the Display Message Line to indicate
that the SQ-Elite-8T is sequencing boilers to protect the return from dropping below the
Minimum Return.
•
Most condensing boilers will run more efficient with cooler return temperatures. In this
case, select the Of option on the Minimum Return to allow the monitoring of the return
on the display without sequencing the boiler stages.
RETURN LAG
Adjustable from 0 to 30 minutes
Default:
2 minutes
Hold Button:
MENU/Min. Return/Return Lag
in Heating only
•
It is the time it takes for the system return to change after sequencing the stages.
•
Initially, adjust this value to equal the Reaction Time. Then, in extreme cold weather
monitor the return making sure it is about 10°F above the Minimum Return setting and
adjust it if needed.
SYSTEM SETTINGS
Hold Button:
MENU/<System Settings>
The System Settings menu provides access to adjusting and fine-tuning the system for
enhanced comfort and better fuel savings. The SQ-Elite behaves differently based on the
selected Control Modes (See Startup Settings 27).
PROGRAM CHANGE SETTINGS
To be able to change the SQ-Elite settings the Program/Run Switch must be set to Program.
The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring
Cover can be securely closed using a padlock.
Outdoor Temperature (in °F)
70 60 50 40
20
30
0
-10
10
-20
120
140
130
150
160
170
180
100
110
W
ater
Temperature (in °F)
Custom Reset Ratio
Point1: System=120°F
Oudoor=60°F
Point2: System=170°F
Oudoor=0°F
Point1
Point2
Customized Reset Ratio
Max Target
Min Target
70
60
50
40
30
20
10
0
-10
-20
120
140
130
150
160
170
180
100
110
Water
Temperature (in °F)
Outdoor Temperature (in °F)
Offset=10°F
Reset Ratio=1.5 : 1.0
Reset Ratio
Max Target
Min Target
Reset Ratio + 10F Offset
Min Target=120°F
Max Target=170°F
---- MIN TARGET ----
70 F
[
]
BACK
SAVE
---- MAX TARGET ----
240 F
[
]
BACK
SAVE
---- MIN RETURN ----
120 F
[
]
BACK
SAVE
---- RETURN LAG ----
2min
[
]
BACK
SAVE
- SYSTEM SETTINGS -
<Stage Settings>
<Setback Schedule>
<DHW Settings>
Setback
0 F
Run-On
2min
Pump Exercise Off
BACK
SELECT
Connecting SQ-Elite to Two Extension Panels
and 4-20mA EMS Interface using RS485
SQ-Elite
SQ-Elite-8
SEQUENCING CONTROL
SYSTEM
DHW PUMP
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
SYS=
144
F OD=
35
F
<AB > DE GH JK
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
STAGE
MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25
26
37
38
PROVE
SYSTEM
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
COMB. AIR
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT A
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT B
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
4-20 mA EMS
4-20mA INPUT
+
Signal GND
1
2
3
RS485
EXTENSION
CONNECTORS
4-20mA EMS Interface
4-20mA
EMS Signal
(+)
(-)
6 Pin Phone Cable (provided with Extension)
6 Pin Phone Cable (provided with 4-20mA EMS Interface)
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
-- STAGE SETTINGS --
Reaction Time 1min
Purge Delay 0.0min
Min Runtime 2min
Standby Delay
10min
Last Stage Hold
5 F
Throttle
2 F
<Lead Settings>
BACK
SELECT
-- REACTION TIME --
2min
[
]
BACK
SAVE
--- PURGE DELAY ----
0.0min
[
]
BACK
SAVE
- MINIMUM RUNTIME -
2min
[
]
BACK
SAVE
---- RETURN LAG ----
2min
[
]
BACK
SAVE
- SYSTEM SETTINGS -
<Stage Settings>
<Setback Schedule>
<DHW Settings>
Setback
0 F
Run-On
2min
Pump Exercise Off
BACK
SELECT
Connecting SQ-Elite to Two Extension Panels
and 4-20mA EMS Interface using RS485
SQ-Elite
SQ-Elite-8
SEQUENCING CONTROL
SYSTEM
DHW PUMP
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
SYS=
144
F OD=
35
F
<AB > DE GH JK
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
STAGE
MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25
26
37
38
PROVE
SYSTEM
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
COMB. AIR
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT A
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT B
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
4-20 mA EMS
4-20mA INPUT
+
Signal GND
1
2
3
RS485
EXTENSION
CONNECTORS
4-20mA EMS Interface
4-20mA
EMS Signal
(+)
(-)
6 Pin Phone Cable (provided with Extension)
6 Pin Phone Cable (provided with 4-20mA EMS Interface)
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
-- STAGE SETTINGS --
Reaction Time 1min
Purge Delay 0.0min
Min Runtime 2min
Standby Delay
10min
Last Stage Hold
5 F
Throttle
2 F
<Lead Settings>
BACK
SELECT
-- REACTION TIME --
2min
[
]
BACK
SAVE
--- PURGE DELAY ----
0.0min
[
]
BACK
SAVE
- MINIMUM RUNTIME -
2min
[
]
BACK
SAVE
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1 2
RUN
PROGRAM
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 12VA MAX
INPUT RATINGS:
USE COPPER CONDUCTORS ONLY
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3 4 5 6 7 8 9 10 11 12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30 31
L N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
Mini-MOD
-------- SETTINGS ----
Season
Winter
Set Point
70
o
F
<System Settings>
<Maintenance>
<History>
<System Startup>
BACK
SELECT
--- SENSOR TYPE ---
Set Point
o
F
Set Point
o
C
Reset
o
F
Reset
o
C
BACK
▲
▼
SAVE
- EMS INPUT MODE -
Disable
Enable
BACK
▲
▼
SAVE
-EMS 4ma SETPOINT -
120
o
F
[
]
BACK
▲
▼
SAVE
-EMS 20ma SETPOINT-
220
o
F
[
]
BACK
▲
▼
SAVE
-- OUTPUT A TYPE --
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
▲
▼
SAVE