14
|
059063–00 REV. C
05
INSTALLATION
RETURN SENSOR WIRING OPTIONAL
(AVAILABLE IN HEATING ONLY)
•
If the Return Sensor is connected, must be purchased separately, the SQ-Elite-8T will recognize
it and alternate its temperature on the display with the Target temperature. If the Return
temperature is below the Minimum Return, the SQ-Elite-8T will sequence stages based on the
Return Sensor, Minimum Return, Calculated Target, and the actual System Temperature.
•
The Return on the SQ-Elite-8T is designed to be connected to a temperature sensor that can
be purchased separately (HT #904250–00) for immersion in a 3/8ID well (P/N 350147–00 or
P/N 904011–00).
•
The sensor wires can be extended up to 500’ using shielded 2-conductor cable (Belden #8760
or equivalent (#18/2)).
•
Temperature sensors have no polarity. Connect the wires from the outdoor sensor to the
SQ-Elite-8T terminals marked OUTDOOR TEMP - 31, 32.
•
Connect the shield to the circled terminal 32 with one of the sensor wires. Do not connect it to
the sensor.
WIRING THE DOMESTIC HOT WATER (DHW) SENSOR
•
The DHW input can be used to raise system Set Point to 200°F or Maximum Target, whichever
is lower. The DHW Piping on page 28 must be selected from the Startup Menu to determine
the DHW Priority options.
•
DHW Call terminals can be connected to either a dry-contact or a temperature sensor that can
be purchased separately (HT #904250–00) for immersion in a 3/8ID well (P/N 350147–00
or P/N 904011–00).
•
If using a dry contact, wire an aquastat or other controls to provide dry-contact closure on the
DHW terminals.
•
If using a sensor, the sensor wires can be extended up to 500’ using shielded 2-conductor cable
(Belden #8760 or equivalent (#18/2)).
•
Temperature sensors have no polarity. Connect the wires from the DHW sensor to the
SQ-Elite-8T terminals marked DHW - 33, 34. Connect the sensor shield to the circled
terminal 34 with one of the sensor wires. Do not connect the shield to the sensor.
•
If Shutdown was selected as the External Input, any DHW call will be ignored when the
Shutdown is active.
WIRING THE SHUTDOWN
•
This feature will only be available when Shutdown is selected as the External Input Mode
option from the Startup menu on page 29.
•
This feature can be used whenever it is desirable to turn off the SQ-Elite-8T stage outputs from
a remote location or another controller (i.e. EMS input).
•
When the Shutdown is enabled, all active stages will immediately turn off. The System Pump,
Combustion Air, and unit pumps’ or valves’ relays will remain energized for the Run-On delay
period and then turn off.
•
The Shutdown signal must be a dry contact input. No voltage can be placed across the
SHUTDOWN terminals.
•
Bring the two wires from the dry contact to the SHUTDOWN - 35, 36 terminals.
•
When Shutdown is selected, Setback will be available using the programmed
Day/Night schedule.
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
Sensor Shiled
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Return Sensor
Shutdown
Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
Outdoor Sensor
Prove Dry Contact
Shutdown Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
PWR
L N
1 2
3
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
33
35
20
22
28
30
34
36
25
26
37
38
PROGRAM
RUN
23 24
SYS
AUX
OUT
Auxiliary
Input2
Outdoor
Temp
System
4-20mA
+ -
PROVE
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input1
Auxiliary
Input3
T-Stat
Dry Contact
PWR
L N
1 2
3
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
33
35
20
22
28
30
32
34
36
25
26
37
38
PROGRAM
RUN
23 24
SYS
AUX
OUT
Auxiliary
Input2
Outdoor
Temp
System
4-20mA
+ -
PROVE
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input1
Auxiliary
Input3
PWR
L N
1 2
3
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
33
35
20
22
28
30
32
34
36
25
26
37
38
PROGRAM
RUN
23 24
SYS
AUX
OUT
Auxiliary
Input2
Outdoor
Temp
System
4-20mA
+ -
PROVE
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input1
Auxiliary
Input3
Cut the Green,
White, and Clear
Tube
Connect
to 1/4" pigtail
BLACK
RED
Transducer
4-20mA
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
PWR
L N
1 2
3
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
33
35
20
22
28
30
32
34
36
25
26
37
38
PROGRAM
RUN
23 24
SYS
AUX
OUT
Auxiliary
Input2
Outdoor
Temp
System
4-20mA
+ -
PROVE
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input1
Auxiliary
Input3
Setback Dry Contact
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback
Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove
Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Return Sensor
Shutdown
Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
Outdoor Sensor
Prove Dry Contact
Shutdown Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
PWR
L N
1 2
3
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
33
35
20
22
28
30
34
36
25
26
37
38
PROGRAM
RUN
23 24
SYS
AUX
OUT
Auxiliary
Input2
Outdoor
Temp
System
4-20mA
+ -
PROVE
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input1
Auxiliary
Input3
T-Stat
Dry Contact
PWR
L N
1 2
3
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
33
35
20
22
28
30
32
34
36
25
26
37
38
PROGRAM
RUN
23 24
SYS
AUX
OUT
Auxiliary
Input2
Outdoor
Temp
System
4-20mA
+ -
PROVE
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input1
Auxiliary
Input3
PWR
L N
1 2
3
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
33
35
20
22
28
30
32
34
36
25
26
37
38
PROGRAM
RUN
23 24
SYS
AUX
OUT
Auxiliary
Input2
Outdoor
Temp
System
4-20mA
+ -
PROVE
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input1
Auxiliary
Input3
Cut the Green,
White, and Clear
Tube
Connect
to 1/4" pigtail
BLACK
RED
Transducer
4-20mA
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
PWR
L N
1 2
3
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
33
35
20
22
28
30
32
34
36
25
26
37
38
PROGRAM
RUN
23 24
SYS
AUX
OUT
Auxiliary
Input2
Outdoor
Temp
System
4-20mA
+ -
PROVE
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input1
Auxiliary
Input3
Setback Dry Contact
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
Sensor Shiled
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback
Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N
Line
Neutral
120VAC
Power Source
Sensor Shiled
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
35
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Outdoor Sensor
Prove
Dry Contact
Sensor Shiled
System Sensor
Sensor Shiled
Return Sensor
Shutdown Dry Contact
DHW Sensor
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
System
Pump
DHW
Pump
PWR
L N
1 2
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
27
29
31
DHW
33
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
23 24
COMB.
AIR
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
T-Stat Dry Contact
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
SENSORS MUST BE GOLD SERIES
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
SYSTEM
OUTDOOR
TEMP
SHUTDOWN
/TSTAT
/SETBACK
RETURN
TEMP
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
25
26
37
38
PROVE
TEMP
PROGRAM
RUN
OUTPUT RATING: 6 AMP RESISTIVE,
1 AMP PILOT DUTY PER OUTPUT AT 120VAC.
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
Setback Dry Contact
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
Comb.
Air
Damper
L
N
L
N
L
N
L
N