60
|
059063–00 REV. C
14
SPECIFICATIONS
Voltage Input
120 VAC 60 Hz
Power Consumption
12 VA Max
Operating Temperature
20°F/-7°C to 120°F/49°C
Operating Humidity
20% to 80%
Dimensions
11”W x 9” H x 3 ¾” D
Weight
2.5 pounds
SQ-ELITE SPECIFICATIONS
Lead Stage Rotation
Time ( 1 to 999 Hours (41 days)), Manual, First-On/First-Off
SQ-Elite-8 Outputs and LEDs
11 N.O. S.P.S.T (8 Stages, 1 System, 1 DHW Pump, 1 Combustion Air)
SQ-Elite-8 Inputs
1 Sys(Temp), 1 Outdoor, Return Temp, DHW Temp, Ext Setback/Shutdown, Prove
Stage Modes
Auto, Standby, Off, On
Standby Time (PID only)
1 to 60 minutes
Output Built-in Relay Ratings
2 Amp inductive (Maximum of 1/4 HP) at 120 VAC 60 Hz
Add-On SQ-Elite-EXT Panels
Up two SQ-Elite-EXT Panels using RS485
Temperature Display
Fahrenheit or Celsius.
Display
Graphical Alphanumeric (7 rows x 21 char. each)
Temperature Sensor Ranges
-35°F to 250°F
Outdoor Cutoff Range
20°F/-17°C to 100°F/38°C, ON and OFF
Set Point
-10°F/-23°C to 230°F/110°C
External Set Point
-10°F/-23°C to 240°F/116°C using 4–20mA EMS Interface (optional)
Reset Ratio Range (Outdoor Reset Only)
(1:4) to (8:1) (Outdoor : System Water), and Custom
Reset Ratio Offset Adjustment (Outdoor Reset Only)
Minus -40°F/-22°C to plus 40°F/22°C
Minimum Target (Outdoor Reset Only)
70°F/21°C to 170°F/77°C
Maximum Target (Outdoor Reset Only)
90°F/38°C to 240°F/116°C
Reaction Time (PID only)
1 to 10 minutes
Minimum Run-Time (PID only)
0 to 60 minutes
Purge Delay (PID only)
0.0 to 10.0 minutes
Last Stage Hold (PID only)
0°F/0°C to 30°F/17°C
Throttle Range (OSS only)
2°F/1°C to 20°F/11°C
Domestic Hot Water Priority Options
Parallel Piping with Priority or without Priority and Primary Secondary
Pump Run-On
0 to 60 minutes
Pump Exercise
Yes or No
Schedules
1 Day and 1 Night (Setback) settings per day
Night Setback
0°F/0°C to 80°F/44°C
Power Backup
Lithium coin battery, 100 days minimum 5 year replacement (Maintains Clock in power outages)
External Inputs
Shutdown Input, and Prove Input. (Dry Contacts Only)
Season
Winter and Summer
SQ-ELITE-EXT SPECIFICATIONS
Extension Numbering
Toggle Switch A or B
LED
1 Power (Dual Color Green (A)/Red (B)), 1 Communication, 8 Stage Output relays (Dual Color Green (A)/Red (B))
Stage Outputs
8 N.O. S.P.S.T.
Output Built-in Relay Ratings
2 Amp inductive (Maximum of 1/4 HP) at 120 VAC 60 Hz
Connection to SQ-Elite and another SQ-Elite-EXT
Two RS485