059063–00 REV. C
|
27
STARTUP SETTINGS
Can be accessed by holding down the Menu
button for over three seconds.
PROGRAM CHANGE SETTINGS
To be able to change the SQ-Elite settings the Program/Run Switch must be set to Program.
The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring
Cover can be securely closed using a padlock.
STARTUP SEQUENCE
Hold Button:
MENU/<System Startup>
•
When powered, the SQ-Elite performs a self-test on its components. After the self-test
diagnostics have been successfully completed, the SQ-Elite will initialize the panel.
•
On the first power up, the System Startup screen will appear after the initialization is
complete. If it doesn’t, the SQ-Elite has already been configured
•
The System Startup menu sets the main parameters as the type of sensor, the type of
output whether heating or cooling, the sequencing mode, and many other parameters
described in this section.
•
Before entering the Startup menu, several warnings will alert you to the consequences of
making Startup changes.
CONTROL MODE
Outdoor Reset, Set Point, EMS 4–20mA
Default:
Outdoor Reset
Hold Button:
MENU/<System Startup>/..../Control Mode
•
Outdoor Reset provides a variable set point based on outdoor temperature. Available for
Heating applications only.
•
Outdoor Reset mode requires the use of an outdoor sensor. DO NOT select Outdoor
Reset without an outdoor sensor.
•
Set Point mode does not require an outdoor sensor. If an outdoor sensor is connected in
Set Point mode it will be used only as an Outdoor Cutoff point. That is, to turn the stages,
system, and Comb. Air relays off.
•
The EMS 4–20mA allows the SQ-Elite-8T to receive an external set point from an EMS/
BMS system. This option requires the use of the 4–20mA EMS Interface (HT# 926741–00).
•
You must select the 4mA (min) and 20 mA (max) Set Point values in the following screens.
•
Connect the 4–20mA EMS Interface to the SQ-Elite-8T RS485 connection using the
phone cable provided with the 4–20mA EMS interface.
DISPLAY UNIT
ºF, ºC
Default:
ºF
Hold Button:
MENU/<System Startup>/..../Display Unit
•
The SQ-Elite-8T can control boilers and chillers in hydronic environment where the
temperature is the critical factor. It allows the user to display temperature information and
settings in either ºF (Fahrenheit) or ºC (Celsius). Select the display unit that is best suited
for your application.
WARNING
A good practice after
performing any Startup
menu modifications is to
check all operating settings
and adjustments to match
the new settings.
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1 2
RUN
PROGRAM
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 12VA MAX
INPUT RATINGS:
USE COPPER CONDUCTORS ONLY
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3 4 5 6 7 8 9 10 11 12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30 31
L N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
Mini-MOD
-------- SETTINGS ----
Season
Winter
Set Point
70
o
F
<System Settings>
<Maintenance>
<History>
<System Startup>
BACK
SELECT
--- SENSOR TYPE ---
Set Point
o
F
Set Point
o
C
Reset
o
F
Reset
o
C
BACK
▲
▼
SAVE
- EMS INPUT MODE -
Disable
Enable
BACK
▲
▼
SAVE
-EMS 4ma SETPOINT -
120
o
F
[
]
BACK
▲
▼
SAVE
-EMS 20ma SETPOINT-
220
o
F
[
]
BACK
▲
▼
SAVE
-- OUTPUT A TYPE --
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
▲
▼
SAVE
10
INSTALLER MENU SEQUENCE
Connecting SQ-Elite to Two Extension Panels
and 4-20mA EMS Interface using RS485
SQ-Elite
SQ-Elite-8
SEQUENCING CONTROL
SYSTEM
DHW PUMP
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
SYS=
144
F OD=
35
F
<AB > DE GH JK
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
STAGE
MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25
26
37
38
PROVE
SYSTEM
TEMP
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
COMB. AIR
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT A
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT B
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
4-20 mA EMS
4-20mA INPUT
+
Signal GND
1
2
3
RS485
EXTENSION
CONNECTORS
4-20mA EMS Interface
4-20mA
EMS Signal
(+)
6 Pin Phone Cable (provided with Extension)
6 Pin Phone Cable (provided with 4-20mA EMS Interface)
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
ARE YOU SURE?
No
Yes
BACK
SAVE
---- CONTROL MODE ---
Outdoor Reset
Set Point
EMS 4-20mA
BACK
SAVE
---- DISPLAY UNIT ---
F
C
BACK
SAVE
EMS 4mA SET POINT
100 F
[
]
BACK
SAVE
EMS 20mA SET POINT
170 F
[
]
BACK
SAVE
Connecting SQ-Elite to Two Extension Panels
and 4-20mA EMS Interface using RS485
SQ-Elite
SQ-Elite-8
SEQUENCING CONTROL
SYSTEM
DHW PUMP
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
SYS=
144
F OD=
35
F
<AB > DE GH JK
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
STAGE
MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25
26
37
38
PROVE
SYSTEM
TEMP
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
COMB. AIR
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT A
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT B
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
4-20 mA EMS
4-20mA INPUT
+
Signal GND
1
2
3
RS485
EXTENSION
CONNECTORS
4-20mA EMS Interface
4-20mA
EMS Signal
(+)
(-)
6 Pin Phone Cable (provided with Extension)
6 Pin Phone Cable (provided with 4-20mA EMS Interface)
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
ARE YOU SURE?
No
Yes
BACK
SAVE
---- CONTROL MODE ---
Outdoor Reset
Set Point
EMS 4-20mA
BACK
SAVE
---- DISPLAY UNIT ---
F
C
BACK
SAVE
EMS 4mA SET POINT
100 F
[
]
BACK
SAVE
EMS 20mA SET POINT
[
]
BACK
SAVE
Connecting SQ-Elite to Two Extension Panels
and 4-20mA EMS Interface using RS485
SQ-Elite
SQ-Elite-8
SEQUENCING CONTROL
SYSTEM
DHW PUMP
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11
13
Stage E
15
Stage F
17
Stage D
6
8
10
12
14
16
18
RS485
SYS=
144
F OD=
35
F
<AB > DE GH JK
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27
29
31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20
22
28
30
32
34
36
STAGE
MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25
26
37
38
PROVE
SYSTEM
TEMP
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
COMB. AIR
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT A
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
L N
1 2
I
3 4
J
5 6
K
7 8
L
9 10
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q
S
U
R
T
V
SQ-Elite-EXT B
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W
X
4-20 mA EMS
4-20mA INPUT
+
Signal GND
1
2
3
RS485
EXTENSION
CONNECTORS
4-20mA EMS Interface
4-20mA
EMS Signal
(+)
(-)
6 Pin Phone Cable (provided with Extension)
6 Pin Phone Cable (provided with 4-20mA EMS Interface)
SQ-Elite-EXT
SEQUENCING CONTROL EXTENSION
ARE YOU SURE?
No
Yes
BACK
SAVE
---- CONTROL MODE ---
Outdoor Reset
Set Point
EMS 4-20mA
BACK
SAVE
---- DISPLAY UNIT ---
F
C
BACK
SAVE
EMS 4mA SET POINT
100 F
[
]
BACK
SAVE
EMS 20mA SET POINT
170 F
[
]
BACK
SAVE