059063–00 REV. C
|
53
12
TROUBLESHOOTING
TEMPERATURE INPUTS
DISPLAY SHOWS SENSOR OPEN
Check the sensor is connected and the wires are continuous to the SQ-Elite-8T. Finally follow the procedure for Incorrect
Temperature Display.
DISPLAY SHOWS SENSOR SHORT
The SQ-Elite-8T sees a short across the input terminals. Remove the wires from the sensor terminals. The display should change to
read OPEN. If it doesn’t, the SQ-Elite-8T may be damaged.
DISPLAY SHOWS AN INCORRECT TEMPERATURE DISPLAY
Remove the wires from the sensor terminals. The display should change to read OPEN. If it doesn’t, the SQ-Elite-8T may be
damaged. Take an ohm reading across the detached sensor wires. Take an ohm reading across the detached sensor wires. The ohm
reading should correspond to the Temperature sensor Table. If it does not, the sensor may be damaged.
RETURN SENSOR DOES NOT DISPLAY TEMPERATURE
Check the sensor is connected and the wires are continuous to the SQ-Elite-8T. Finally follow the procedure for Incorrect
temperature display.