STARTUP MENU—HOT WATER
DHW TEMP SETPOINT
Selections:
140°F–200°F
Default:
140°F
Description:
On a DHW call, the Genesis Heat-Timer
®
will raise the System target
temperature to the DHW Temp Set Point until the DHW call expires.
SET WAKE TIME
Selections:
1:00–12:00 am/pm
Default:
6:00 am
Description:
The Genesis Heat-Timer
®
has two levels of heat. The Day (WAKE/RETURN)
level is used when a building is occupied and people are active. The Night (AWAY/SLEEP)
level is used when a building is not occupied, or when people are sleeping. Additional
Day (WAKE/RETURN) periods can be set in the Schedule menu, providing each day
period a Day (WAKE) time setting and a Day (RETURN) time setting.
SET WAKE TEMP
Selections:
51°F–90°F
Default:
72°F
Description:
The Wake Temp is the desired building space temperature when the
building is occupied and people are active. The Genesis Heat-Timer
®
will adjust the
system temperature based on the outdoor temperature as required to achieve this
target building space temperature. This setting is a basic initial setting, additional
desired Wake temp settings along with Return temp settings can be made in the
Schedule menu.
SET SLEEP TIME
Selections:
1:00–12:00 am/pm
Default:
10:00 pm
Description:
The Genesis Heat-Timer
®
has two levels of heat. The Day (WAKE) level is
used when a building is occupied and people are active. The Night (SLEEP) level is used
when a building is not occupied, or when people are sleeping. Additional Night (SLEEP)
periods can be set in the Schedule menu, providing each day period a Night (AWAY)
time setting and a Night (SLEEP) time setting.
SET SLEEP TEMP
Selections:
51°F–90°F
Default:
70°F
Description:
The Sleep Temp is the desired building space temperature when
the building is unoccupied or when people are inactive or asleep. The Genesis
Heat-Timer
®
will adjust the system temperature based on the outdoor temperature
as required to achieve this target building space temperature. This setting is a basic
initial setting, additional desired Sleep temp settings along with Away temp settings
can be made in the Schedule menu.
SET WAKE TEMP.
BACK SAVE
F
06:00 am
SET WAKE TIME
BACK NEXT
DHW TEMP SETPOINT
BACK SAVE
F
10:00 pm
SET SLEEP TIME
BACK NEXT
SET SLEEP TEMP.
BACK SAVE
F