WIRING
MSI COMPONENTS INTERFACE WIRING
(TERMINALS 28, 29)
1
Run an 18 AWG multi-conductor, shielded or twisted-pair cable (Heat-Timer P/N 703001–01 or equivalent #18/2 cable)
through a knockout on the MSI sensor interface Enclosure to the Genesis Heat-Timer
®
module. Ensure the wires are routed
through the knockouts on the Genesis enclosure and are separated from high voltage wiring.
•
Connect the MSI Interface terminal M+ to the Genesis Heat-Timer
®
terminal M+ (28).
•
Connect the MSI Interface terminal M– to the Genesis Heat-Timer
®
terminal M– (29).
MSI COMPONENT WIRING
The Genesis Heat-Timer
®
can be expanded to accept one MSI component such as a Boiler Feed Meter, or Stack Sensor or Pressure
and Vacuum Sensor using MSI interface. These components are viewed remotely through ICMS web page.
NOTE
Reference the proper MSI component Installation and Operation Manual for additional wiring information of the sensor.
MSI Interface Module
Stack Sensor