059705–00 REV. B
|
49
17
STARTUP MENU—HOT WATER
HEATING SYSTEM MENU
Selections:
Steam, Hot Water
Default:
Hot Water
Description:
Sets the type of application the Genesis Heat-Timer
®
will be controlling—
STEAM or HOT WATER.
HEATING SYSTEM—
HOT WATER
Selections:
On/Off Boiler
Default:
On/Off Boiler
Curr Volt Boiler
Floating Valve
Curr Volt Valve
Description:
The Genesis Heat-Timer
®
can provide a simple ENABLE output for
any burner that is ON-OFF operation. The Genesis Heat-Timer
®
can also provide a
modulating input for a burner that requires a current voltage input such as 4–20mA,
0–10V, 2–10V and 0–5V.
For applications in which the Genesis Heat-Timer
®
controls a 3-way mixing valve, the
Genesis Heat-Timer
®
can provide a SPDT output for valves with a floating actuator.
For valves with a proportional actuator, the Genesis Heat-Timer
®
can provide a current
voltage output of 4–20mA, 0–10V, 2–10V 1–5V and 0–5V.
MODULATING TYPE
Selections:
0–10V
Default:
0–10V
2–10V
0–5V
1–5V
4–20mA
Description:
Select the current or voltage output signal to match the burner or
valve modulation. This selection is only available if the Heating System is Hot Water
Curr Volt Boiler or Curr Volt Valve.
HEATING SYSTEM
BACK SAVE
Steam
Hot Water
HEATING SYSTEM
BACK SAVE
On/Off Boiler
Curr Volt Boiler
Floating Valve
Curr Volt Valve
MODULATION TYPE
BACK SAVE
0-10v
2-10v
0-5v
1-5v
4-20ma