32
|
059705–00 REV. B
1
Apply power to the Genesis Heat-Timer
®
once all wiring has been completed.
2
Perform initial programming of the Genesis Heat-Timer
®
.
See “Initial Programming of the Genesis Heat-Timer
AUTO/BYPASS SWITCH
•
The BYPASS switch (1) must be in the AUTO position for the Genesis Heat-Timer
®
to control the heating system.
•
The BYPASS position overrides all automatic control of the Genesis Heat-Timer
®
control.
•
If the Genesis Heat-Timer
®
has power and is operational, switching to BYPASS automatically activates the Motorized Valve, the
Burner, and the System output.
•
Switching the control to BYPASS manually during a power outage, activates the Motorized Valve, Burner, and System outputs.
COMPLETING THE INSTALLATION
After the Genesis Heat-Timer
®
is powered-on and the initial programming is complete:
1
Replace the Genesis Heat-Timer
®
enclosure wiring cover and secure it in place with two screws.
2
Optionally secure the enclosure using a padlock with a maximum shank diameter of 1/8”.
1
ALERT
Switching the Genesis Heat-Timer
®
into BYPASS overrides all automatic operation. In BYPASS, the boiler will run
constantly on its own limits or the valve will be fully open.
13
POWERING-ON