SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Panel Control Sequence
1. When power is provided to the 120V terminals connected to the power module
1
, the transformer provides 24V power
to the StatLink® Base Module.
2. When the thermostat calls for heat, its internal 24V contacts close, the StatLink® Base Module dry contacts
2
close, and
the pump
3
turns on. If actuator(s)
4
are connected to the thermostat's zone, the actuator(s) will open.
3. When the requirements of the thermostat are met, the internal contacts of the thermostat open, the StatLink® Base
Module dry contacts open, and the circulator stops. If actuator(s)
4
are connected to the thermostat's zone, the
actuator(s) will close.