Heat
Link
www.heatlink.com
12
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
1
(3.78)
0.1
(0.38)
3
(11.36)
0.5
(1.89)
0.01
(0.04)
0.05
(0.19)
Mass Flow Rate in US gpm (L/min)
1 (3)
5 (15)
0.1 (0.3)
0.5 (1.5)
0.01
0.05 (0.15)
Pressure Dr
op in ft H
2
O
(kP
a)
10 (30)
30 (90)
(0.03)
1
0.5
0.25
Stainless Steel Manifold # of turns from closed position
0.75
1.5
2
3.5
Working loop flow ranges from 0.1 to 1.25 US gpm (0.38 to 4.7 L/m) for floor heating and from 1.5 to 2.5 US gpm (5.7 to 9.5
L/m) for snowmelting. Pressure drop must be closely checked when water flow is beyond the upper working range.
76100 Series (Flow Meter) Friction Head Graph