SSPxx000x – SS Manifold Pump Panels

Installation, Operation, and Maintenance

Supply Manifold

Secondary Balancing (Fine Tuning).

CCW = open

CW = close

CCW = open

CW = close

Return Manifold

Primary Balancing.

Black cap for manual shut-off only.

Use drip cap 

 for balancing.

Balancing Method 1:

Valve setting or flow characteristic 

known (pre-balancing)

1.  Fully open supply valve (flow 

meter) [factory open].

2.  Close return valve completely 

[factory open].

3.  Open return valve the number of 

turns as per heatloss calculation or 

friction head graph.

4.  After all valves are set, field 

adjustments may be necessary.

Notes:

•  Hose bib thread is an ASME thread.

•  After fill procedure: the drip cap 

 should be 

placed back on to the hose bib 

.

•  Pipe to manifold connectors sold separately.

Balancing Method 2:

Only flow rate known

1.  Ensure all supply valves are open 

[factory open].

2.  Ensure all return valves are open 

(remove black cap).

3.  Use the return valve to adjust flow 

to desired setting (flow meter).

4.  Valves adjusted first may need to 

be re-adjusted once all other loops 

have been set.

Remove locking cap to adjust flow meter.

Please note:
Do not use tools to adjust flow 
meters. (Damage to the flow meter 
will occur, and will not be covered 
under warranty).

Balancing Notes:

Return :  Use for primary balancing purposes and manual shut-off. Use drip cap 

to adjust the return manifold.

➀➁ 

 

Caution: Opening the return valve too far will result in removing 

the valve stem.

Supply :  Use for secondary balancing / fine tuning the flow rate. Remove 

locking cap to adjust the flow meter by hand, do not use tools.

Flow meter balancing adjustment range: 

0-1.5 US gpm or 0-5 L/min.

Stainless Steel Manifold

Specifications:

• Material: Stainless Steel EN 1.4301 (X5CrNi18-10) which is equivalent to SAE 304 (V2A)

• Maximum Trunk Flow Rate:  18 US gpm (4.1 m3/h)

• Maximum Circuit Flow Rate:  76100 Series - 1.5 US gpm (0.34 m

3

/h)

 

76200 Series - 2.5 US gpm (0.57 m

3

/h)

2

1

1

CCW = open

CW = close

76200 

Series

76100 

Series

Содержание SSPLR106T

Страница 1: ...e Manual Heat Link L6SSPxx000x MECHANICAL ROOM IN A BOX SSPLR106T SSPSS106B 120 140 160 180 200 100 80 60 40 C F 0 20 100 40 80 60 LIVE GROUND NEUTRAL CAUTION 115 VOLTS ONLY 120 140 160 180 200 100 80...

Страница 2: ...acking 5 Panel Components 6 7 Specifications 8 Panel Component Specifications 9 14 Manifold Balancing 11 Recessed Housing Mounting 15 16 Surface Mount Housing Mounting 17 Piping Hookup 18 Fill and Pur...

Страница 3: ...tion of the panel and your safety Please pay attention to these symbols Disclaimer HeatLink Group Inc shall not be responsible for errors in its brochures or printed materials HeatLink Group Inc reser...

Страница 4: ...ion of factors such as BTU loads outdoor design temperature indoor design temperature room set point temperature s differential fluid temperatures head loss flow rates and transfer capacities of the h...

Страница 5: ...by removing the strapping Step 3 Remove the cardboard spacers from the carton then remove the panel from the carton Lift the panel by the enclosure not the cover Step 4 Remove the cover from the pane...

Страница 6: ...0 76930 76930 6 Isolation Ball Valve 7 120V ac terminal strip 8 24V ac 40VA Transformer 9 StatLink Base Module 40226 40226 40226 10 Enclosure Recessed or Surface Mount Recessed or Surface Mount Recess...

Страница 7: ...nce 11 15 120 140 16 0 180 200 100 80 60 40 C F 0 20 100 40 80 60 LIVE GROUND NEUTRAL CAUTION 115 VOLTS ONLY 106030C 120 140 16 0 180 200 100 80 60 40 C F 0 20 100 40 80 60 LIVE GROUND NEUTRAL CAUTION...

Страница 8: ...system controller 110 V ac max current 3A Auxiliary terminal Yes Piping 1 piping Piping connections 1 FNPT Enclosure Galvanized steel visible parts are satin coated steel Recessed Surface Mount 4 6 lo...

Страница 9: ...e 40226 The StatLink base module connects room thermostats to their corresponding actuators Each zone has an LED which indicates if it is calling for heat A timer thermostat 46643 or 46673 can send a...

Страница 10: ...m Head feet 1st Speed 2nd Speed 3rd Speed Circulator The circulators moves the heated fluid through the hydronic system when there is a call for heat from the thermostat Factory set to 3rd speed Speci...

Страница 11: ...ll return valves are open remove black cap 3 Use the return valve to adjust flow to desired setting flow meter 4 Valves adjusted first may need to be re adjusted once all other loops have been set Rem...

Страница 12: ...01 0 05 0 15 Pressure Drop in ft H 2 O kPa 10 30 30 90 0 03 1 0 5 0 25 Stainless Steel Manifold of turns from closed position 0 75 1 5 2 3 5 Working loop flow ranges from 0 1 to 1 25 US gpm 0 38 to 4...

Страница 13: ...e Stainless Steel Manifold of turns from closed position 1 3 78 0 1 0 38 5 18 9 0 5 1 89 0 01 0 04 0 05 0 19 Mass Flow Rate in US gpm L min 1 3 5 15 0 1 0 3 0 5 1 5 0 01 0 05 0 15 Pressure Drop in ft...

Страница 14: ...ing water is used for hydronic systems Specifications Adjustment Range 0 05 0 5 bar 1 67 16 73 ft H2 O 106030C SSASLEM Optional Installed StatLink 4 Zone Expansion Module 40234 The StatLink 4 zone exp...

Страница 15: ...e knockouts Recessed Enclosure Mounting Step 1 Use a screwdriver or similar thin tool through the hole to bend the mounting tabs out 90 degrees from the enclosure 42 1 2 7 8 O D 7 8 O D 2 14 13 16 27...

Страница 16: ...me This panel is heavy 2 3 person lift required Step 5 Complete the supporting frame by adding a top plate Be sure to drill corresponding holes in the top plate if any knockouts were removed Step 6 Se...

Страница 17: ...aw a straight line on the wall and mark the stud locations If the housing cannot be secured directly to the studs or suitable backing boards plywood may need to be installed behind the housing to prop...

Страница 18: ...Lubricate the inside of the manifold port with silicone o ring lubricant 79952 sold separately 2 Cut the PEX tubing at a 90 angle 3 Place the Nut and Split Ring Ferrule onto the PEX tubing Note For th...

Страница 19: ...lves Fully open valve D Step 3 Attach a purge hose not included to D Pressurize the main supply line Open valve B Step 4 Open the first return manifold valve F Open the first supply manifold valve E W...

Страница 20: ...g 2 Wire Thermostat battery only or non electric 3 Wire Thermostat HeatLink thermostats 4 Wire Thermostat with dry contact signal W R C 1 2 1 1 2 2 24 V Signal W R C 1 2 1 1 2 2 24 V 24 V Signal W R C...

Страница 21: ...When the thermostat calls for heat its internal 24V contacts close the StatLink Base Module dry contacts 2 close and the pump 3 turns on If actuator s 4 are connected to the thermostat s zone the act...

Страница 22: ...heat Use a stethoscope or similar device to verify The StatLink module or circulator may be defective A qualified electrician should verify 24V power is supplied to the thermostats and actuator The 2...

Страница 23: ...es regulations and authorities have final jurisdiction Rough in wiring see Wiring detail see SSP Panel T Heat Source e g Boiler or Heat Exchanger SCH SSP M010 2013 10 08 Generic SSP Series Radiant Hea...

Страница 24: ...etc for heat source as per local codes Use isolation ball valves for all circuits and components Local codes regulations and authorities have final jurisdiction Rough in wiring see Wiring detail see S...

Страница 25: ...355 HeatLink Mixing Reset Control 2 1 Com 3 No Power Cls Opn 6 IN 7 Com 8 MIX 9 Com 10 OUT 11 Pwr C 12 Pwr R 13 Sys Pump 17 Boiler 18 Mix Sensor Supply Outdoor Sensor Boiler Contacts 4 Timer 5 15 Dem...

Страница 26: ...h particular control chosen In all cases manufacturer equipment schematics will take precedence over HeatLink electrical schematics Local codes regulations and authorities have final jurisdiction Appl...

Страница 27: ...Heat Link 27 www heatlink com SSPxx000x SS Manifold Pump Panels Installation Operation and Maintenance...

Страница 28: ...al Phone 852 25693213 Fax 852 25359271 Ireland Distributed by Jamoni Ltd Phone 057 932 4062 Fax 057 932 4063 Freephone 1800 311338 M xico Distributed by Distribuidora Caisa S A de C V Phone 52 55 3300...

Отзывы: