Heat
Link
www.heatlink.com
18
SSPxx000x – SS Manifold Pump Panels
Installation, Operation, and Maintenance
Piping Hookup
Step 1
Before making any connections, identify the
required connections to and from the panel.
Step 2
Connect mains piping using 1" MNPT fittings.
Note: Use precautions when soldering or
applying heat within 16" of the panel.
120 140
16
0
180
200
100
80
60
40
°C
°F
0
20
100
40
80
60
LIVE
GR
OUND
NEUTRAL
CAUTION 115 VOLTS ONLY
Primary
Return
Primary
Supply
Floor Return
Floor Supply
SSPLR106T shown
Step 3
Connect all tubing to manifold adapters. (77100 series connecters sold separately)
1. Lubricate the inside of the manifold port with silicone o-ring lubricant (#79952 sold separately).
2. Cut the PEX tubing at a 90˚ angle.
3. Place the Nut and Split Ring Ferrule onto the PEX tubing.
Note: For the
3
⁄
4
" connecter, the Split RIng Ferrule must be placed inside the Nut before putting them onto the
PEX tubing.
Method A
5. Push the Brass Insert onto the PEX tubing as far as it will go.
6. Push the PEX tubing with Brass Insert as far as it will go into the manifold module. Ensure the o-ring is clean and
take care not to pinch it.
Method B
5. Push Brass Insert as far as it will go into the manifold. Ensure the o-ring is clean and take care not to pinch it.
6. Push PEX tubing onto the Brass Insert as far as it will go.
7. Use a wrench to tighten the nut.
90°
Brass Insert with
O-ring
Split Ring Ferrule
Nut