![HBK CB1010 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/hbk/cb1010/cb1010_operating-manual_2111690015.webp)
13
CANHEAD
BUS CONFIGURATION
Maximum configuration
per ML74B
max. 12 CANHEADs, corresponding to 120 measuring points
Per
MGCplus system
250 e.g. 500 measuring points
1)
The maximum number of 256 channels per MGCplus system must not be exceeded. The number of
channels may be distributed among several ML74B. The maximum number of channels per CP42 and
CP52 is 256, with up to 512 channels possible if a CP52 is combined with an NT040 power supply.
5.2
Device Net specifications
More detailed specifications for Device Net (bus topology, drop lines, etc.), can be found
on the Internet site www.odva.org
→
Devicenet
→
Planning and Installation Manual
Notice
The maximum CAN bus line length must not exceed 250 m at the 250^kBaud setting and
100 m at the 500^kBaud setting,
see also technical Datasheet.
A drop line must be no longer than 15 m (but if possible, drop lines should be avoided).
TR
TR
Power
Supply
TR
trunk line
drop lines
device or node
terminating resistor
Fig. 5.2
Line bus and drop lines (example from the DeviceNet Manual)
Содержание CB1010
Страница 1: ...CANHEAD ENGLISH DEUTSCH Operating Manual Bedienungsanleitung...
Страница 3: ...CANHEAD ENGLISH DEUTSCH Operating Manual...
Страница 40: ...CANHEAD CONFIGURING WITH MGCPLUS 38 S Serial number and bridge type of the connected module...
Страница 52: ...CANHEAD CANHEAD ENHANCEMENTS 50...
Страница 53: ...CANHEAD ENGLISH DEUTSCH Bedienungsanleitung...
Страница 91: ...39 CANHEAD KONFIGURIEREN MIT MGCPLUS S Seriennummer und Br ckentyp des angeschlossenen Moduls...
Страница 103: ...51 CANHEAD CANHEAD ERWEITERUNGEN...
Страница 104: ...HBK Hottinger Br el Kjaer www hbkworld com info hbkworld com A01185 13 X00 00 7 0102 0010...