USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
1-888-HAY-INDL (1-888-429-4635)
ISHCP3000FC Rev A 11/30/16
Pg. 8 of 16
www.haywardflowcontrol.com
Hayward Flow Control
Electrical Specs
Use copper conductors only. For indoor & outdoor use.
60 Hz Electrical Data
PUMP MODEL
RATED HP
TOTAL HP
PHASE
VOLTAGE
AMPS
1APSES16
2
2.7
1
208-230
8.7-8.5
1APSES36
2
2.7
3
208-230/460
6.1-6.0/3.0
1APSES36H
2
2.7
3
575
2.4
1APSES17
3
3.45
1
208-230
11.7-11.5
1APSES37
3
3.45
3
208-230/460
9.2-9.0/4.5
1APSES37H
3
3.45
3
575
3.8
1APSES18
5
5.5
1
208-230
21.0-20.0
1APSES38
5
5.5
3
208-230/460
13.6-13.2/6.6
1APSES38H
5
5.5
3
575
5.4
1APSES39
7
7.49
3
208-230/460
19.8-17.2/8.6
1APSES39H
7
7.49
3
575
7.2
50 Hz Electrical Data
PUMP MODEL
RATED HP
TOTAL HP
PHASE
VOLTAGE
AMPS
1APSES16
2
2
1
220-240
8.9-8.7
1APSES36
2
2
3
190/380-415
6.8/3.4-3.5
1APSES17
3
3
1
220-240
12.1-12.4
1APSES37
3
3
3
190/380-415
10.0/5.0-5.0
1APSES38
5
5
3
190/380-415
15.4/7.7-7.9
1APSES39
7
7
3
190/380-415
21.0/10.5-9.9
Voltage
Voltage at motor
MUST NOT
be more than 10% above or below motor name plate rated voltage, or motor may overheat,
causing overload tripping and reduced component life. If voltage is less than 90% or more than 110% of rated voltage when
motor is running at full load, consult power company.
Grounding and Bonding
Install, ground, bond, and wire motor in accordance with local or national electrical code requirements.
Permanently ground motor. Use green ground terminal provided under motor canopy or access plate; use size and type wire
required by code. Connect motor ground terminal to electrical service ground.
Bond motor to system structure. Bonding will connect all metal parts within and around the system with a continuous wire.
Bonding reduces the risk of a current passing between bonded metal objects, which could potentially cause electrical shock if
grounded or shorted.
Reference NEC codes for all wiring standards including, but not limited to, grounding, bonding
and general wiring procedures.
Use a solid copper conductor, size 8 or larger. Run wire from external bonding lug to reinforcing rod or mesh. Connect a
No. 8 AWG (8.4 mm
2
) [No. 6 AWG (13.3 mm
2
) for Canada]
solid copper bonding wire to the pressure wire connector
provided on the motor housing and to all metal parts of system, and to all electrical equipment, metal piping (except gas
piping), and conduit within 5 ft. (1.5 m) of system.