Examples of chimney heights required for fire safety regulations.

Ðèñóíîê 2.  Ïðèìåðû òðåáîâàíèé ïîæàðíîé áåçîïàñíîñòè ê âûñîòå äûìîõîäà.

2. Protective distances

The protective distance between the inflammable 

structures and the chimney outer casing must be 

minimum 100 mm. In lead-through the chimney 

and the roof structures have to be filled with fire-

resistance rated mineral wool. If the connecting 

pipe in the forward end is of non-isolated 

material, the protective distance from this pipe 

to inflammable construction materials needs to 

be 1000 mm. Furthermore, the isolated chimney 

should be visible up to a minimum 

of 430 mm (figure 3).

If the chimney is connected to a 

sauna stove equipped with a pipe-

model water tank, the bare  part of 

the smoke pipe must be equipped 

with a radiation cover (figure 4). 

The water tank installation should 

follow the protective distances 

from the mounting instructions.

In case the protective distance 

requirements for the furnace 

are higher than for the chimney 

the distance can be reduced 

by installing non-flammable 

protective plates. The protective 

distance requirements are 

specified in the installation 

manual. A single flange halves the 

protective distance and a double 

flange to a quarter. Either a 7.0 

mm non-flammable wallboard or a 

minimum 1.0 mm metal sheet can 

be used for such light protection. 

The board or sheet gap from the 

protected, inflammable material 

must be minimum 30 mm and 

the air circulation secured in 

the gap through the lower and 

upper end of the protecting 

construction. If a double flange 

protective plate is used, a 30 mm 

gap should be constructed using 

bushing manufactured out of non-

flammable materials allowing free 

air circulation through the upper 

and lower end of the plates. 

More detailed instructions 

available from the local fire 

authorities.

2. Áåçîïàñíîå ðàññòîÿíèå

Áåçîïàñíîå ðàññòîÿíèå ìåæäó âîñïëàìåíÿþùèìèñÿ 
êîíñòðóêöèÿìè è âíåøíåé ñòàëüíîé ðóáàøêîé 
äûìîõîäà äîëæíî ñîñòàâëÿòü íå ìåíåå 100 ìì. Ïðè 
ïðîâåäåíèè ïðîõîäà ðàññòîÿíèå ìåæäó äûìîõîäîì 
è êîíñòðóêöèÿìè êðûøè äîëæíî áûòü çàïîëíåíî 
îãíåñòîéêîé ìèíåðàëüíîé âàòîé.  Åñëè â íà÷àëüíîé 
÷àñòè äûìîõîäà áûëà èñïîëüçîâàíà ïðîìåæóòî÷íàÿ 
òðóáà áåç èçîëÿöèè, áåçîïàñíîå ðàññòîÿíèå ìåæäó 
äàííûì ó÷àñòêîì äûìîõîäà è âîñïëàìåíÿþùèìèñÿ 

êîíñòðóêöèÿìè, ñîãëàñíî òðåáîâàíèÿì 
ïîæàðíîé áåçîïàñíîñòè, âîçðàñòàåò äî 1000 
ìì.  Íåîáõîäèìî ó÷èòûâàòü, ÷òî â ïîìåùåíèè 
ó÷àñòîê âèäèìîé èçîëèðîâàííîé òðóáû 
äîëæåí ñîñòàâëÿòü íå ìåíåå 430 ìì (ðèñ. 3).

Åñëè äûìîõîä ïîäñîåäèíÿåòñÿ ê êàìåíêå, 

îñíàùåííîé âîäîíàãðåâàòåëåì òðóáíîãî 
òèïà, òî íåèçîëèðîâàííóþ ÷àñòü âíóòðåííåé 
òðóáû íåîáõîäèìî çàùèòèòü ýêðàíîì 
òåïëîâîãî èçëó÷åíèÿ (ðèñ. 4). Ïðè ìîíòàæå 
ðåçåðâóàðà äëÿ âîäû íåîáõîäèìî ó÷èòûâàòü 
òðåáîâàíèÿ ê áåçîïàñíûì ðàññòîÿíèÿì.

Åñëè òðåáîâàíèÿ ê áåçîïàñíîìó ðàññòîÿíèþ 

òîïêè âûøå, ÷åì ó äûìîõîäà, òî áåçîïàñíîå 
ðàññòîÿíèå ìîæíî óìåíüøèòü ñ ïîìîùüþ 
çàùèòíîé ïëàñòèíû, èçãîòîâëåííîé èç 

íåãîðþ÷èõ ìàòåðèàëîâ. Òðåáîâàíèÿ ê 
áåçîïàñíûì ðàññòîÿíèÿì òîïêè óêàçàíû 
â èíñòðóêöèè ïî åå ìîíòàæó. Îäèíàðíàÿ 
çàùèòà ñîêðàùàåò áåçîïàñíîå ðàññòîÿíèå 
âïîëîâèíó, à äâîéíàÿ çàùèòà – äî îäíîé 
÷åòâåðòîé ÷àñòè. Îäèíàðíóþ çàùèòó ìîæíî 
èçãîòîâèòü èç íåãîðþ÷åãî ñòðîèòåëüíîãî 
ëèñòà, ïîäõîäÿùåãî äëÿ ýòèõ öåëåé, 
òîëùèíîé íå ìåíåå 7,0 ìì è ìåòàëëè÷åñêîãî 
ëèñòà òîëùèíîé íå ìåíåå 1,0 ìì. Ìåæäó 
âîñïëàìåíÿþùèìñÿ ìàòåðèàëîì è çàùèòíûì 
ýëåìåíòîì íåîáõîäèìî îñòàâèòü çàçîð íå 
ìåíåå 30 ìì, îáåñïå÷èâàþùèé ñâîáîäíóþ 
öèðêóëÿöèþ âîçäóõà ìåæäó âåðõíèìè è 
íèæíèìè ïëàñòèíàìè çàùèòíîãî ýëåìåíòà. 
Ïðè èñïîëüçîâàíèè äâóõñëîéíîé çàùèòû 
ìåæäó ëèñòàìè íåîáõîäèìî, ñ ïîìîùüþ, 
íàïðèìåð, ðàñïîðíûõ âòóëîê èç íåãîðþ÷åãî 
ìàòåðèàëà, îñòàâèòü çàçîð íå ìåíåå 30 ìì, 
îáåñïå÷èâàþùèé ñâîáîäíóþ öèðêóëÿöèþ 
âîçäóõà ìåæäó îáåèìè ïëàñòèíàìè çàùèòíîãî 
ýëåìåíòà. 

Çà áîëåå ïîäðîáíûìè èíñòðóêöèÿìè ìîæíî 

îáðàòèòüñÿ â ìåñòíûå îðãàíû ïîæàðíîé 
áåçîïàñíîñòè.

Radiation cover

Çàùèòà îò òåïëîâîãî 

èçëó÷åíèÿ

Figure 3.

Ðèñóíîê 3

.

min. 430 mm

ìèí. 430 ìì

Содержание WHP1500

Страница 1: ...07032006H Instructions for installation of Steel Chimney Steel Chimney EN RU Harvia Oy PL12 40951 Muurame Finland www harvia fi...

Страница 2: ...Standard delivery Steel Chimney extensions WHP500 Length 0 5 m Length of isolated component 470 mm 0 5 470 Steel Chimney 1 5 m 1 5 Smoke pipe 1 0 m stainless steel 1 0 Lead through flange Note Extens...

Страница 3: ...el Chimney 6 4 Installing the rain flange 7 5 Installing the rain cap 8 6 Installing the lead through flange 8 1 4 2 5 3 6 4 7 5 8 6 8 EN RU 0809 Harvia Oy PL 12 40951 Muurame Finland 06 0809 CPD 0548...

Страница 4: ...ere is no need for protection if the chimney is installed in a sauna The chimney shouldn t be encapsulated The maximum height of the steel chimney is five metres while the permissible maximum for the...

Страница 5: ...nces from the mounting instructions In case the protective distance requirements for the furnace are higher than for the chimney the distance can be reduced by installing non flammable protective plat...

Страница 6: ...nwards in the pipe E Lock the outer casing in place with three self boring screws Bore the screws through the metal sockets F Join the upper end with three self boring screws Bore the screws through t...

Страница 7: ...e chimney on the surface of the roof Soap solution can be used as a lubricant if needed C Mould the brims of the rain flange carefully fitting it to the roof profile D Spread some silicone underneath...

Страница 8: ...ng the lead through flange The two piece lead through flange fixed in horizontal or pitched ceilings trims the edges of the opening The lead through flange is best suited for roof pitches of under 1 1...

Отзывы: