█ When turn the power ON after completing wiring

Operation Method

 (1) After the firmware version of the temperature controller appears for a short period of time, the operation 

     mode is running like the number ① that process value (current temperature) 

      and the set value are displayed.
 (2)  In the number ①, if         button is pressed for 3 seconds, it enters         

      display setting   mode. 

      It can be selected as DISP 1, DISP 2 and DISP 3 to limit displaying setting groups.

 (3)  In the operation mode, if            button is pressed, the output amount is displayed like the picture ⑤ - ⑥ below.

POWER ON

Output amount 

display

⑤Heating-

   Cooling type

⑥ Standard type

for 3 

seconds

for 3 

seconds

for 3 seconds

● Switching between modes

How to set access levels [Level (LEVL)] and a group display [Display (dISP)]
- Setting group configuration parameters are displayed according to the group display 
   [Display (dISP)] setting.
- Setting group is editable depending on setting Access Level [Level (LEVL)].

Access level [Level (LEVL)]
LEVL 3 : parameter values can be changed for all setting groups with the key of controller in front.
LEVL 2 : parameter values can not be changed for output group and input group with 
            the key of controller in front.
LEVL 1 : parameter values can not be changed for Auto-tuning group(G.At), PID  
            group(G.PId), Alarm Group (G.ALM), retransmission group(G.trn), communication  
            group(G.CoM), output group(G.oUt), input group (G.In) with the key of controller in front.

Caution

In the operation mode, if         and       button are pressed simultaneously for 3 seconds, 
it enters           setting mode which prevents an operator to change parameter setting as 
limiting access to the group. The default is 3rd level. The level setting mode limits the 
display setting mode.

 Control group

Symbol 

Parameter

Option 

Available 

condition Default

Control group

Options for control mode

-

-

Zone setting

OFF / ON

Control 

output: PID

OFF

Ramp function type

A / B

Always on

A

Ramp rising temperature OFF/ EUS (0 ~ 100%)

Ramp 

function 

type A

OFF

Ramp falling temperature OFF/ EUS (0 ~ 100%)

OFF

Ramp time unit

HOUR / MIN

HOUR

Ramp rising temperature OFF/ EUS (0 ~ 100%)

Ramp 

function 

type B

OFF

Ramp rising time

0.01 ~ 99.59(hh.mm)

0.01

Ramp falling temperature OFF/ EUS (0 ~ 100%)

OFF

Ramp falling time

0.01 ~ 99.59(hh.mm)

0.01

External contact input

OFF / ON

Always on

OFF

Hot key setting

AT / A-M

AT

Auto/manual setting

AUTO / MAN 

(1)

AUTO

Control mode 

TRAD / 2DOF

TRAD

2DOF

Alpha coefficient 

0 ~ 100 %

Control 

mode: 

2DOF

50 %

Factory reset function

0/1 [PASSWORD: 1304] 

(2)

Always on

0

 Set value (SV) setting group

 Auto-tuning (AT) group

Symbol

Parameter 

Option 

Available 

condition Default

 P.I.D group

Symbol

Parameter 

Option

Available 

condition Default

PID group

Options for PID mode

-

-

ANTI RESET 
WIND-UP setting

Auto /  50.0 ~ 200.0 %

PID 

control

100 %

PID group setting

0 / 1 ~ 3

Always on  

0

n. Proportional band (P) 0.1(H/C TYPE : 0.0) ~ 999.9 %

Selecting one 
of PID groups

5.0 %

n. Integral time (I)

OFF / 1 ~ 6000 s

Always on  240 s 

n. Derivative time (D)

OFF / 1 ~ 6000 s

Always on  60 s

 

n. Manual reset

-5.0 ~ 105.0 %

Integral time: 

OFF

50.0 %

n. Proportional band (PC) 
for cooling

0.0(ON/OFF) / 0.1 ~ 999.9 %

heating·

cooling

5.0 %

n. Integral time (IC) for 
cooling

OFF /  1 ~ 6000 s

240 s 

n. Derivative time (DC) for 
cooling

OFF / 1 ~ 6000 s

60 s 

n. hysteresis (dead band) -100.0 ~ 50.0 %

3.0 %

n. Zone position setting

EU(0) < 1.RP  < 2.RP  < 
EU(100 %)

PID group 1 

or 

PID group 2

EU

(100 %)

 Heater Break Alarm (HBA) group

 Alarm group

Symbol

Parameter 

Option 

Available 
condition

Default

Alarm group

Options for alarm mode

-

-

Alarm 1 type setting OFF /  1 ~ 21 

Refer to “Alarm type and code”

 

Always on

1

Alarm 2 type setting

2

Hysteresis (dead band) 

of alarm 1

EUS(0 ~ 100 %)

EUS

(0.5 %)

Hysteresis (dead band) 

of alarm 2

Set value of alarm 1 Absolute alarm : 

EU(-100 ~ 100 %)
Deviation alarm : 
EUS(-100 ~ 100 %)

EU

(100 %)

Set value of alarm 2

EU

(0 %)

 Retransmission (RET) group

Symbol 

Parameter 

Option 

Available 

condition 초기값

RET. Group

Options for RET. Group.

-

-

Retransmission type
or power for sensor

Process value(PV) / set value 

(SV) / output amount (MV) / 

power for sensor (SPS)

RET. 

option

PV

Retransmission value 4 - 20 mA / 0 – 20 mA  (1) 

-

4 - 20 mA

High limit of 

retransmission

TC / RTD: FR-H ~ FR-L
DC voltage: SL-H ~ SL-L
( Must be RET.H > RET.L )

PV / SV

EU(100 %)

Low limit of

retransmission

EU(0 %)

(1)  If you want retransmission 0-5V, a 250 Ω 0.1% resistor must be connected to retransmission output terminal.
     If you want retransmission 0-10V, a 500 Ω 0.1% resistor must be connected to retransmission output terminal.

(1) When manual output function is selected with 'ON', 'AT indicator' lights on at the front panel.
      (When auto-tuning (AT) is running, 'AT indicator' flashes at the front panel)
(2) when "1" is selected in factory reset function, PASSWORD is displayed. After input the  
       PASSWORD [1304], controller power turns off and on for initializing parameter values.

Auto-tuning group Options for auto-tuning (AT) group

-

-

Auto-tuning type 
setting

Standard (STD) :           
Low PV (LOW) :          

Control 

output: 

PID

STD

Auto-tuning start 
setting

OFF / 1 ~ 3 /                  (AUTO)

OFF

Symbol 

Parameter 

Option 

Available 

condition Default

Set value setting group

Options for set values

-

-

Set value Number
setting

1~3 (the chosen set value is 
displayed and controlled)

Always 

on 

1

Set value 1 (SV1) setting EU (0 ~ 100 %)

EU(0 %)

Set value 2 (SV2) setting EU (0 ~ 100 %)

EU(0 %)

Set value 3 (SV3) setting EU (0 ~ 100 %)

EU(0 %)

Symbol

Parameter 

Option 

Available 

condition

Default

Heater break alarm group

Options for HBA mode.

-

-

Current setting of HBA output

OFF /  1 ~ 50 A

HBA 

Option 

(Refer to 

“model 

name and 

code” 

table)

OFF

Hysteresis setting of HBA 
output

0 ~ 50

EUS

(0.5 %)

Current measurement value of 
HBA output

Only indicates current measurement 
value (0 ~ 50 A)

Содержание HX4

Страница 1: ... it is not possible please use shielded wires for the input signal wires For thermocouple TC please use ungrounded sensors There is a possibility of malfunction of the product by electric leakage if a grounded sensor is used If there is a lot of noise from the power line installing an insulated transformer or a noise filter is recommended The noise filter should be grounded on the panel and the wi...

Страница 2: ...99 9 4 E 1 100 0 999 9 5 T 1 199 9 400 0 6 R 0 1700 7 B 2 0 1800 8 S 0 1700 9 L 1 100 0 900 0 10 N 200 1300 1 0 of FS 1 Digit 11 U 1 199 9 400 0 0 5 of FS 1 Digit 12 W 0 2300 13 Platinel II 0 1390 Resistance temperature detector RTD 20 KPt100 Ω 3 199 9 500 0 0 5 of FS 1 Digit 21 Pt100 Ω 3 199 9 640 0 22 Pt100 Ω 3 200 640 DC voltage VDC DC 30 1 000 5 000 V DC 1999 9999 Scaling function SL H SL L ne...

Страница 3: ...ns for PID mode ANTI RESET WIND UP setting Auto 50 0 200 0 PID control 100 PID group setting 0 1 3 Always on 0 n Proportional band P 0 1 H C TYPE 0 0 999 9 Selecting one of PID groups 5 0 n Integral time I OFF 1 6000 s Always on 240 s n Derivative time D OFF 1 6000 s Always on 60 s n Manual reset 5 0 105 0 Integral time OFF 50 0 n Proportional band PC for cooling 0 0 ON OFF 0 1 999 9 heating cooli...

Страница 4: ...NC Hold 21 Heater break alarm 1 HBA1 Meaning of auto tuning AT start in auto tuning Group G At is as follows 1 is auto tuning for SV1 2 is auto tuning for SV2 3 is auto tuning for SV3 AUTO proceed with the Auto tuning in the order of the SV1 SV2 SV3 Function Description Function 1 Auto tuning Auto tuning is a function that the controller automatically measures the characteristics of the target sys...

Страница 5: ...t up low alarm is active when temperature is rising with power ON If you select alarm hold function there is no limit alarm ON during the temperature rise until set point Note If you want to use the alarm hold function please set proper parameter referring to alarm group G ALM Function 4 Ramp function Ramp function Type A Select A in Ramp function type rMP t parameters of control group G CtL The r...

Страница 6: ...u 3 Press SET key for 3 sec to go back to operation screen Function 15 HOT key This function is for activating deactivating most frequently used function on operation screen 1 Press SET UP key for 3 sec to activate hot key function 2 Press SET UP key for 3 sec again to deactivate hot key function One of the following two functions can be assigned as hot key function from the hot key select menu HK...

Страница 7: ...ime 0 6000 sec PID Group 0323 2 MR PID group 2 manual reset 5 0 105 0 2 PID Group 0324 2 PC PID group 2 cooling proportional band 0 0 999 9 2 PID Group 0325 2 IC PID group 2 cooling integral time 0 6000 sec PID Group 0326 2 DC PID group 2 cooling derivative time 0 6000 sec PID Group 0327 2 DB PID group 2 Heating Cooling dead band 100 0 50 0 2 PID Group 0328 2 RP PID group 2 zone position setting E...

Страница 8: ...SG RTD OUT REL 1 2 3 4 5 7 8 10 11 12 9 6 SV2 SV3 OUT1 SSR SCR RET OUT2 SSR SCR RET POWER 100 240 V 50 60 H 7 8 9 10 1 2 3 4 5 11 6 12 13 14 15 16 17 18 OUT1 RTX RTX OUT1 SSR SCR RET CT SV2 OUT2 SSR SCR RET POWER 100 240 V 50 60 Hz 5 5 VA A AL1 AL2 B B TC 11 12 Current Voltage CT SV3 HX9 HX3 HX4 HX7 HX2 OUT1 RELAY AL1 AL2 13 14 15 16 1 2 3 4 5 7 8 10 11 12 22 23 24 9 19 20 21 17 6 18 A B B SV2 TC ...

Отзывы: