background image

-2-

Input code for input type and range

Setting Mode

®

DISP 1

DISP 2

DISP 3

1   2   3

Power On

1) Operation

mode

Process value

Set value

Process value

Output amount

PV

SV

PV

SV

Control group

Auto-tuning group

Setting value group

PID group

Alarm group

RET. group

COM. group

Output group

Input group

HBA group

for 3 seconds

for 3 seconds

for 3 seconds

for 3 seconds

for 

3 seconds

HOTKEY

+

Level

+

Quick menu

+

Ramp 
function 
type A

Ramp 
function 
type B

※ In the standard type, Retransmission output (RET) is only available from OUT2. 

(1) Standard type 

Type

Output 

code

OUT1(Heating)

OUT2

Default

Relay

SSR/SCR/RET

Relay

SSR/SCR/RET

Standard

Type

0

Control output

(ON/OFF)

-

AL2

(Alarm 2

output)

RET

(retransmission

output)

1

1

-

SSR

2

SCR(4 - 20 mA)

3

Control output 

(PID)

-

Input signal 

Input signal 

Input type

Range (℃)

Accuracy

Note

Thermocouple

(TC)

1

K     

*1

-200 ~ 1370

±0.5 % of FS ±1 Digit

•FS is the measurable range
  from the maximum to the minimum 
  for each range.

• Digit is the minimum display value

❇1  below 0 ℃ :
                ±1.0 % of FS ± 1 digit

❇2 0 ~ 400℃ range :
                ±10 % of FS ± 1 digit

❇3  20 → KPt100 Ω (C1603)
      21, 22 → Pt100 Ω(IEC751) 

 *4 In case of using Current input,   
  Resistor 250 Ω 0.1 % should be 
  installed in the input terminal.

2

K      

*1

-199.9 ~ 999.9

3

J     

*1

-100.0 ~ 999.9

4

E      

*1

-100.0 ~ 999.9

5

T      

*1

-199.9 ~ 400.0

6

R      

0 ~ 1700

7

B      

*2

0 ~ 1800

8

S  

0 ~ 1700

9

L      

*1

-100.0 ~ 900.0

10

N

-200 ~ 1300

±1.0 % of FS ±1 Digit

11

U      

*1

-199.9 ~ 400.0

±0.5 % of FS ±1 Digit

12

W

0 ~ 2300

13

Platinel II

0 ~ 1390

Resistance

temperature

detector

(RTD)

20

KPt100 Ω

*3

-199.9 ~ 500.0

±0.5 % of FS ±1 Digit

21

Pt100 Ω       *3

-199.9 ~ 640.0

22

Pt100 Ω

*3

-200 ~ 640

DC voltage

(VDC / ㎷ DC)

30

1.000 - 5.000 V DC

-1999 ~ 9999

Scaling function(SL-H/SL-L) necessary

±0.5 % of FS ±1 Digit

31

0.0 - 100.0 ㎷ DC

DC current

30

     4 - 20 ㎃ DC *4

█ Control Output Composition

HX series is a multi-control-output temperature controller. It can have relay ON/OFF, 
SSR voltage pulse output, 4 – 20 mA current output as a control output by selecting an option in the parameter.
If the option is chosen like below in the output parameter (             ) of the output group (          ) in standard temperature controller
0 : Relay ON/OFF control is as a control output.
1  : SSR output is as a control output.
2 : 4 – 20 mA DC current output is as a control output.
3 : Relay PID control is as a control output.

(2) Heating / Cooling Type ( simultaneous control)

Type

Output

code

OUT1(Heating)

OUT2

Default

Relay

SSR/SCR/RET

Relay(AL2)

SSR/SCR/RET

Heating / 

Cooling 

type

4

-

SSR

AL2

(Alarm 2

output )

SSR

4

5

-

SCR(4 - 20 mA)

6

Control 

output (PID)

RET 

(retransmission 

output)

7

-

SSR

SCR

(4 - 20 mA)

8

-

SCR(4 - 20 mA)

9

Control 

output (PID)

RET 

(retransmission 

output)

10

-

SSR

Control output 

(PID)

RET

(Retransmission

output)

11

-

SCR(4 - 20 mA)

12

Control 

output (PID)

-

Содержание HX4

Страница 1: ... it is not possible please use shielded wires for the input signal wires For thermocouple TC please use ungrounded sensors There is a possibility of malfunction of the product by electric leakage if a grounded sensor is used If there is a lot of noise from the power line installing an insulated transformer or a noise filter is recommended The noise filter should be grounded on the panel and the wi...

Страница 2: ...99 9 4 E 1 100 0 999 9 5 T 1 199 9 400 0 6 R 0 1700 7 B 2 0 1800 8 S 0 1700 9 L 1 100 0 900 0 10 N 200 1300 1 0 of FS 1 Digit 11 U 1 199 9 400 0 0 5 of FS 1 Digit 12 W 0 2300 13 Platinel II 0 1390 Resistance temperature detector RTD 20 KPt100 Ω 3 199 9 500 0 0 5 of FS 1 Digit 21 Pt100 Ω 3 199 9 640 0 22 Pt100 Ω 3 200 640 DC voltage VDC DC 30 1 000 5 000 V DC 1999 9999 Scaling function SL H SL L ne...

Страница 3: ...ns for PID mode ANTI RESET WIND UP setting Auto 50 0 200 0 PID control 100 PID group setting 0 1 3 Always on 0 n Proportional band P 0 1 H C TYPE 0 0 999 9 Selecting one of PID groups 5 0 n Integral time I OFF 1 6000 s Always on 240 s n Derivative time D OFF 1 6000 s Always on 60 s n Manual reset 5 0 105 0 Integral time OFF 50 0 n Proportional band PC for cooling 0 0 ON OFF 0 1 999 9 heating cooli...

Страница 4: ...NC Hold 21 Heater break alarm 1 HBA1 Meaning of auto tuning AT start in auto tuning Group G At is as follows 1 is auto tuning for SV1 2 is auto tuning for SV2 3 is auto tuning for SV3 AUTO proceed with the Auto tuning in the order of the SV1 SV2 SV3 Function Description Function 1 Auto tuning Auto tuning is a function that the controller automatically measures the characteristics of the target sys...

Страница 5: ...t up low alarm is active when temperature is rising with power ON If you select alarm hold function there is no limit alarm ON during the temperature rise until set point Note If you want to use the alarm hold function please set proper parameter referring to alarm group G ALM Function 4 Ramp function Ramp function Type A Select A in Ramp function type rMP t parameters of control group G CtL The r...

Страница 6: ...u 3 Press SET key for 3 sec to go back to operation screen Function 15 HOT key This function is for activating deactivating most frequently used function on operation screen 1 Press SET UP key for 3 sec to activate hot key function 2 Press SET UP key for 3 sec again to deactivate hot key function One of the following two functions can be assigned as hot key function from the hot key select menu HK...

Страница 7: ...ime 0 6000 sec PID Group 0323 2 MR PID group 2 manual reset 5 0 105 0 2 PID Group 0324 2 PC PID group 2 cooling proportional band 0 0 999 9 2 PID Group 0325 2 IC PID group 2 cooling integral time 0 6000 sec PID Group 0326 2 DC PID group 2 cooling derivative time 0 6000 sec PID Group 0327 2 DB PID group 2 Heating Cooling dead band 100 0 50 0 2 PID Group 0328 2 RP PID group 2 zone position setting E...

Страница 8: ...SG RTD OUT REL 1 2 3 4 5 7 8 10 11 12 9 6 SV2 SV3 OUT1 SSR SCR RET OUT2 SSR SCR RET POWER 100 240 V 50 60 H 7 8 9 10 1 2 3 4 5 11 6 12 13 14 15 16 17 18 OUT1 RTX RTX OUT1 SSR SCR RET CT SV2 OUT2 SSR SCR RET POWER 100 240 V 50 60 Hz 5 5 VA A AL1 AL2 B B TC 11 12 Current Voltage CT SV3 HX9 HX3 HX4 HX7 HX2 OUT1 RELAY AL1 AL2 13 14 15 16 1 2 3 4 5 7 8 10 11 12 22 23 24 9 19 20 21 17 6 18 A B B SV2 TC ...