Hanyoung HX4 Скачать руководство пользователя страница 5

-5-

SV3

 150 ℃

Time

External contact 
signal SV2 : ON

External contact 
signal SV3 : ON

SV2

 100 ℃

SV1

  50 ℃

Function 5 : External contact input

This function is used to select one of the set values (SV1, SV2, SV3) by the external contact input 
signal and it is used as the step control.
External contact input should be "ON" to use this function.

20 ㎃

Output signal

12 ㎃

4 ㎃

Output limit (%)

Setting range

Low limit 

(OL-L)

High limit 

(OL-H)

-5 %

50 %

105 %

Function 6 : Output limit

This function is used to set the high limit and low limit as the operating range of the control output.
The output limit (the high limit and low limit) can be set -5 ~ 105 % of the output amount.

Function 7 : Heater break alarm

① This function detects heater break and immediately turns the alarm on.
② Please use the current transformer (CT) designed by Hanyoung NUX.
③ The electric current value and alarm operating point (hysteresis) are set in “HBA group”.
④ This function cannot be used if phase control method (SCR output) is used by thyristor.

Note: If you want to use HBA, please set parameter in HBA group(G.HbA) referring to alarm type and codes.

The dead band of PID control for Heating / Cooling is shown as below.

<PID control for Heating / Cooling: Dead band of “+” set value>

DEAD BAND

Output of heating

Output of cooling

Output (%)

0

100 %

0 %

100 %

0 %

If both heating and cooling are controlled by ON/OFF control, 

the dead band (hysteresis) is shown as below.

<ON/OFF control for heating/cooling>

ON

OFF

ON

HYSTERESIS

HYSTERESIS

DEAD BAND

Heating-side output

Cooling-side output

Function 8 : Heating / Cooling control

In Heating / Cooling control, it divides the PID computation result into two control signals and outputs 
to  heating  and  cooling  output  terminals.  The  control  method  for  each  heating  and  cooling  can  be 
selected either PID control or ON/OFF control. Also, it is possible to choose one of the control outputs: 
relay output, SSR, and current output as the heating output and cooling output.

Also, the dead band of “-” set value and the dead band of PID control for both heating and 
cooling are shown as below. At this time, there is an overlapped output from the both terminals.

<PID control for Heating / Cooling: Dead band of “-” set value>

Output of heating

Output of cooling

Output (%)

0

100 %

0 %

100 %

0 %

DEAD BAND

Function 10 : Alarm hold function

If alarm hold function is not set up, low alarm is active when temperature is rising with power ON.
If you select alarm hold function, there is no limit alarm ON during the temperature rise, until set-point.

Note : If you want to use the alarm hold function, please set proper parameter referring to alarm group(G.ALM).

Function 4 : Ramp function

Ramp function Type: A
Select A in Ramp function type (rMP.t) parameters of control group(G.CtL)
The ramp refers to the gradient that reaches the set value (SV), and the setting 
method is as follows: 
1. Set the desired ramp temperature values in ramp-up and ramp-down temperature settings
2. Set the desired ramp hours or minutes in ramp-time unit setting.
As a result, the gradient of the ramp-up temperature set value / ramp time unit set 
value (or ramp-down temperature set value / ramp time unit value) will reach the set 
value (SV) from the current temperature.

Ramp function Type : B
Select B in Ramp function type(rMP.t) of control group(G.CtL)
This is similar function with Ramp function type A. except that type B sets time in detail, 
0.01~99.59(hh.mm).

100

Time

1

2

3

4

80
60
40

Current temperature  20 ℃

When select ON in Zone of control group(G.CtL) and set the location of temperature in n.rP 
of PID group(G.PID), that distinguishes Zone 1, Zone 2, Zone 3.

Function 2 : PID auto-tuning in Zone

Within the input range, 3 different PID groups can be applied to each of the 3 zones. Since some 
systems have a wide range of temperature to control and the optimal P.I.D values are different for 
their  temperature  ranges,  this  function  can  be  used  to  apply  different  optimal  PID  values  to  their 
temperature ranges.

Max input range 

2.rP

1.rP

Min input range

Zone 3 (PID 3)

Zone 2 (PID 2)

Zone 1 (PID 1)

Time (t)

Function 3 : 2 degree of freedom PID

 

In order to get better response against disturbance in the steady state, there is usually 

a large overshoot in the transient state. To reduce this overshoot in the transient state, 2 
degrees of freedom PID control is used while obtaining good disturbance response in 
the steady state. The parameter “ALPA” is used to control the amount of overshoot.

Select 2-DOF in control mode(Ctr.M) of control group(G.CtL)
If ALPA = 0%, it's same with previous PID control. 
If ALPA = 100%, it may takes long to reach normal state.

ALPA : 

100 %

Time

ALPA : 0 %

Transition

Normal 

state

Step response

Disturbance 

response

SV

Function 9 : Output during emergency

When there is A/D Error or input break (Burn-out), it stops the PID control and outputs the preset 
value. (       parameter in output group)

Содержание HX4

Страница 1: ... it is not possible please use shielded wires for the input signal wires For thermocouple TC please use ungrounded sensors There is a possibility of malfunction of the product by electric leakage if a grounded sensor is used If there is a lot of noise from the power line installing an insulated transformer or a noise filter is recommended The noise filter should be grounded on the panel and the wi...

Страница 2: ...99 9 4 E 1 100 0 999 9 5 T 1 199 9 400 0 6 R 0 1700 7 B 2 0 1800 8 S 0 1700 9 L 1 100 0 900 0 10 N 200 1300 1 0 of FS 1 Digit 11 U 1 199 9 400 0 0 5 of FS 1 Digit 12 W 0 2300 13 Platinel II 0 1390 Resistance temperature detector RTD 20 KPt100 Ω 3 199 9 500 0 0 5 of FS 1 Digit 21 Pt100 Ω 3 199 9 640 0 22 Pt100 Ω 3 200 640 DC voltage VDC DC 30 1 000 5 000 V DC 1999 9999 Scaling function SL H SL L ne...

Страница 3: ...ns for PID mode ANTI RESET WIND UP setting Auto 50 0 200 0 PID control 100 PID group setting 0 1 3 Always on 0 n Proportional band P 0 1 H C TYPE 0 0 999 9 Selecting one of PID groups 5 0 n Integral time I OFF 1 6000 s Always on 240 s n Derivative time D OFF 1 6000 s Always on 60 s n Manual reset 5 0 105 0 Integral time OFF 50 0 n Proportional band PC for cooling 0 0 ON OFF 0 1 999 9 heating cooli...

Страница 4: ...NC Hold 21 Heater break alarm 1 HBA1 Meaning of auto tuning AT start in auto tuning Group G At is as follows 1 is auto tuning for SV1 2 is auto tuning for SV2 3 is auto tuning for SV3 AUTO proceed with the Auto tuning in the order of the SV1 SV2 SV3 Function Description Function 1 Auto tuning Auto tuning is a function that the controller automatically measures the characteristics of the target sys...

Страница 5: ...t up low alarm is active when temperature is rising with power ON If you select alarm hold function there is no limit alarm ON during the temperature rise until set point Note If you want to use the alarm hold function please set proper parameter referring to alarm group G ALM Function 4 Ramp function Ramp function Type A Select A in Ramp function type rMP t parameters of control group G CtL The r...

Страница 6: ...u 3 Press SET key for 3 sec to go back to operation screen Function 15 HOT key This function is for activating deactivating most frequently used function on operation screen 1 Press SET UP key for 3 sec to activate hot key function 2 Press SET UP key for 3 sec again to deactivate hot key function One of the following two functions can be assigned as hot key function from the hot key select menu HK...

Страница 7: ...ime 0 6000 sec PID Group 0323 2 MR PID group 2 manual reset 5 0 105 0 2 PID Group 0324 2 PC PID group 2 cooling proportional band 0 0 999 9 2 PID Group 0325 2 IC PID group 2 cooling integral time 0 6000 sec PID Group 0326 2 DC PID group 2 cooling derivative time 0 6000 sec PID Group 0327 2 DB PID group 2 Heating Cooling dead band 100 0 50 0 2 PID Group 0328 2 RP PID group 2 zone position setting E...

Страница 8: ...SG RTD OUT REL 1 2 3 4 5 7 8 10 11 12 9 6 SV2 SV3 OUT1 SSR SCR RET OUT2 SSR SCR RET POWER 100 240 V 50 60 H 7 8 9 10 1 2 3 4 5 11 6 12 13 14 15 16 17 18 OUT1 RTX RTX OUT1 SSR SCR RET CT SV2 OUT2 SSR SCR RET POWER 100 240 V 50 60 Hz 5 5 VA A AL1 AL2 B B TC 11 12 Current Voltage CT SV3 HX9 HX3 HX4 HX7 HX2 OUT1 RELAY AL1 AL2 13 14 15 16 1 2 3 4 5 7 8 10 11 12 22 23 24 9 19 20 21 17 6 18 A B B SV2 TC ...

Отзывы: