 Output group

Please make sure to choose “input code” in “input code setting” of the input 

group first and then select “output code” in “output type setting” and other 

options in other groups. If “input code” is set later, the options in the other 

groups will be lost.

Caution

Symbol 

Parameter

Option 

Available 

condition

Default

Output group

Options for output type and 
mode

-

-

Output type setting

Refer to “control output 
composition”

Always on 

Std : 1

HC : 4

Output operation

REV: reverse, DIR: direct 

Output code 

0~3

REV

Cycle time

1 ~ 1000 s 

relay : 20s  

SSR : 2 s

Cycle time for cooling

1 ~ 1000 s 

Output code 

4~12

Hysteresis

Standard : EUS(0 ~ 100 %)

ON/OFF 

control 

EUS(0.5 %)

Heating / Cooling: 
0.0 ~ 10.0 %

Heating / 

Cooling

0.5%

Hysteresis type

Cntr / EdGE

ON/OFF 

Control

Cntr

Output amount of
OUT1 when input break

Standard : -5.0 ~ 105.0 %

Always on

0.0 %

Heating - Cooling : 0.0~105.0 %

Output amount of
OUT2 when input break

0.0 ~ 105.0 %

Heating / 

Cooling

0.0 %

High limit of output
amount

Standard : OL-L + 1Digit~ 105.0 %

PID 

control

100.0 %

Heating - Cooling : 0.0 ~ 105.0 %

Low limit of output
amount

Standard : -0.5 % ~ OL-H-1Digit

0.0 %

Heating - Cooling : 0.0 ~ 105.0 %

100.0 %

  Input group

Symbol

Parameter

Option

Available 
condition

Default

Input group

Options for input type and input 
mode

-

-

Input code setting

Input signal and measurable 
range code

Always on

Code : 1

Temperature unit setting ℃ / ℉

TC or RTD

High limit setting

Within range (refer to “input 
code for input type and 
range”) , FR-H > FR-L

Always on 

1370

Low limit setting

-200

Decimal point position
(voltage input)

Fixed for T.C or RTD / DC 
voltage: 0~3 setting for 
decimal point position

Voltage input 

(mV,V)  

1

High limit of scale (voltage 
input)

-1999 ~ 9999 but, SL-H > 
SL-L decimal point according to 
DP-P 

100.0

Low limit of scale (voltage 
input)

0.0

Process value filter

OFF / 1 ~ 120 sec

Always on  

OFF

Process value bias 
(compensation)

EUS(-100 ~ 100 %)

EUS(0 %)

Operation after input 
break (burn-out)

OFF /  UP / DOWN 

UP

(△ : set value,  -▲ : alarm set value,  ▲ : alarm set value)

Hysteresis

Pay atteontion in selecting relay type. Using inverse relay ( such as use nomally closed 

instead of nomally open) will not output anything even though the indicator is on.

Alarm type and code

Code

Alarm type

Operation

1

High absolute value (NO)

2

Low absolute value (NO)

3

High deviation value (NO)

4

Low deviation value (NO)

5

High deviation value (NC)

6

Low deviation value (NC)

7

High-Low deviation value

8

High-Low deviation range

9

High absolute value (NC)

10

Low absolute value (NC)

11

High absolute (NO, Hold)

12

Low absolute (NO, Hold)

13

High deviation (NO, Hold)

14

Low deviation (NO, Hold)

15

High deviation (NC, Hold)

16

Low deviation (NC, Hold)

17

High-Low deviation value (Hold)

18

High-Low deviation range (Hold)

19

High absolute value (NC, Hold)

20

Low absolute value (NC, Hold)

21

Heater break alarm 1 (HBA1)

Meaning of auto-tuning (AT) start in auto-tuning Group(G.At) is as follows:
  1 is auto-tuning for SV1.
  2 is auto-tuning for SV2.
  3 is auto-tuning for SV3.
  - AUTO proceed with the Auto-tuning in the order of the SV1, SV2, SV3.

 Function Description

Function 1 : Auto-tuning

Auto-tuning is a function that the controller automatically measures the characteristics of 
the target system and calculates the optimal values for proportional band (P), integral time 
(I), and derivative time (D) and then sets the optimal values for each PID parameters.
During auto-tuning, the control output is changed to ON/OFF control to get response from 
the target system. From the response, the most appropriate PID values are obtained for 
the system. This is called " Limit Cycle".
HX series has two types of auto-tuning : standard type and low PV type.
① Standard auto-tuning : This auto-tuning is based on the set value (SV).
② Low PV auto-tuning : This auto-tuning is based on the value 10 % lower than the set 
value (SV).

a) Standard auto-tuning

Select auto-tuning type(At.M) with standard(Std) 
in auto-tuning group(G.At)

Set value (SV)

Process value (PV)

Control output ON

ON

ON

Time(t)

Time(t)

Control starts with PID values 

obtained from the auto-tuning

ON/OFF operation

AT start

AT end

Auto-tuning running

OFF

OFF

Select auto-tuning type with PV(LoW) in auto-tuning group (G.At)

b) Low PV auto-tuning

Set value(SV)

Process value (PV)

Control output

operation

Auto-tuning running

ON

ON

ON

Time (t)

SV-10 %

Time (t)

Control starts with 

P.I.D values obtained 

from the auto-tuning

OFF

OFF

Function

 Communication group

Symbol

Parameter 

Option 

Available 

condition

Default

Communication 
group

Options for 
communication mode.

-

-

RS485/RS422 
Protocol

PC.LINK (code : 0) 
PC.LINK SUM (code : 1) 
MODBUS-ASCII (code : 2)
MODBUS-RTU (code : 3)

  Option

0

Communication
speed (BPS)

2400(code : 2), 4800(code : 3), 
9600(code : 4), 14400(code : 5),     
                     19200(code : 6)

4

Parity Bit

NONE(code : 0),
EVEN(code : 1), ODD(code : 2)

1

Stop Bit

1bit (code : 1), 2bit  (code : 2)

1

Data length

7bit  (code : 7), 8bit  (code : 8) 
(code 8 is not available for PC LINK)

8

Address

1 ~ 99 but, max 31 units

1

Response time

0 ~ 10. Response time = 
processing time + 
(response time X 25 ms)

0

※ Please note that frequent communicational data recording may exceed life of EEPROM 
   and cause malfunction.

If you want to use the auto-tuning, there are 2 ways:

  1. When you select the number for set value(SV) you want in start auto-tuning(AT) 

     of auto-tuning Group(G.At), auto-tuning will start.
  2. After selecting auto-tuning(At) in hot-key(Hk.SL) of control group(G.At), auto-tuning will start with  

     pressing hot-key(SET + UP) in the operation mode of controller for 3 seconds and auto-tuning  

     will stop with pressing hot-key(SET+UP) for 3 seconds.
 Note: When auto-tuning(AT) runs, 'AT indicator' flashes at the front panel.

       (When manual output is 'ON', 'AT indicator' lights on steady at the front panel.)

AT start

AT end

*

* Std : Standard, HC : Heating / Cooling

Содержание HX4

Страница 1: ... it is not possible please use shielded wires for the input signal wires For thermocouple TC please use ungrounded sensors There is a possibility of malfunction of the product by electric leakage if a grounded sensor is used If there is a lot of noise from the power line installing an insulated transformer or a noise filter is recommended The noise filter should be grounded on the panel and the wi...

Страница 2: ...99 9 4 E 1 100 0 999 9 5 T 1 199 9 400 0 6 R 0 1700 7 B 2 0 1800 8 S 0 1700 9 L 1 100 0 900 0 10 N 200 1300 1 0 of FS 1 Digit 11 U 1 199 9 400 0 0 5 of FS 1 Digit 12 W 0 2300 13 Platinel II 0 1390 Resistance temperature detector RTD 20 KPt100 Ω 3 199 9 500 0 0 5 of FS 1 Digit 21 Pt100 Ω 3 199 9 640 0 22 Pt100 Ω 3 200 640 DC voltage VDC DC 30 1 000 5 000 V DC 1999 9999 Scaling function SL H SL L ne...

Страница 3: ...ns for PID mode ANTI RESET WIND UP setting Auto 50 0 200 0 PID control 100 PID group setting 0 1 3 Always on 0 n Proportional band P 0 1 H C TYPE 0 0 999 9 Selecting one of PID groups 5 0 n Integral time I OFF 1 6000 s Always on 240 s n Derivative time D OFF 1 6000 s Always on 60 s n Manual reset 5 0 105 0 Integral time OFF 50 0 n Proportional band PC for cooling 0 0 ON OFF 0 1 999 9 heating cooli...

Страница 4: ...NC Hold 21 Heater break alarm 1 HBA1 Meaning of auto tuning AT start in auto tuning Group G At is as follows 1 is auto tuning for SV1 2 is auto tuning for SV2 3 is auto tuning for SV3 AUTO proceed with the Auto tuning in the order of the SV1 SV2 SV3 Function Description Function 1 Auto tuning Auto tuning is a function that the controller automatically measures the characteristics of the target sys...

Страница 5: ...t up low alarm is active when temperature is rising with power ON If you select alarm hold function there is no limit alarm ON during the temperature rise until set point Note If you want to use the alarm hold function please set proper parameter referring to alarm group G ALM Function 4 Ramp function Ramp function Type A Select A in Ramp function type rMP t parameters of control group G CtL The r...

Страница 6: ...u 3 Press SET key for 3 sec to go back to operation screen Function 15 HOT key This function is for activating deactivating most frequently used function on operation screen 1 Press SET UP key for 3 sec to activate hot key function 2 Press SET UP key for 3 sec again to deactivate hot key function One of the following two functions can be assigned as hot key function from the hot key select menu HK...

Страница 7: ...ime 0 6000 sec PID Group 0323 2 MR PID group 2 manual reset 5 0 105 0 2 PID Group 0324 2 PC PID group 2 cooling proportional band 0 0 999 9 2 PID Group 0325 2 IC PID group 2 cooling integral time 0 6000 sec PID Group 0326 2 DC PID group 2 cooling derivative time 0 6000 sec PID Group 0327 2 DB PID group 2 Heating Cooling dead band 100 0 50 0 2 PID Group 0328 2 RP PID group 2 zone position setting E...

Страница 8: ...SG RTD OUT REL 1 2 3 4 5 7 8 10 11 12 9 6 SV2 SV3 OUT1 SSR SCR RET OUT2 SSR SCR RET POWER 100 240 V 50 60 H 7 8 9 10 1 2 3 4 5 11 6 12 13 14 15 16 17 18 OUT1 RTX RTX OUT1 SSR SCR RET CT SV2 OUT2 SSR SCR RET POWER 100 240 V 50 60 Hz 5 5 VA A AL1 AL2 B B TC 11 12 Current Voltage CT SV3 HX9 HX3 HX4 HX7 HX2 OUT1 RELAY AL1 AL2 13 14 15 16 1 2 3 4 5 7 8 10 11 12 22 23 24 9 19 20 21 17 6 18 A B B SV2 TC ...

Отзывы: