HX communication - instructions about the D register address

D-register 

address

Parameter 

name

Parameter meaning

Parameter setting

Parameter 

division

0001

NPV

Current present value (PV)

Read only

*1

Process

0002

NSV

Current set value (SV)

Read only

*1

Process

0004

SSV

Current set value (SV)

Read only

*1

Process

0005

MVOUT

OUT1 control output value of standard type, Total 
control output value of heating/cooling type.

Read only

*2

Process

0006

CH1OUT

OUT1 control output value of standard type,
OUT1 control output value of heating/
cooling type. 

Read only

*2

Process

0007

CH2OUT

OUT2 control output value of heating/
cooling type. 

Read only

*2

Process

0008

PIDNO

When ZONE is OFF, currentlly 
applied set value (SV) and PID group 
number
0001: SV1, PID group 1
0002: SV2, PID group 2
0003: SV3, PID group 3
When ZONE is OFF, currentlly 
applied PID group number
0001: PID group 1
0002: PID group 2
0003: PID group 3

Read only

Process

0009

ALMSTS

Current state of Alarm 1 and Alarm 2:
0000: Alarm 1 OFF, Alarm 2 OFF
0001: Alarm 1 ON, Alarm 2 OFF
0002: Alarm 1 OFF, Alarm 2 ON
0003: Alarm 1 ON, Alarm 2 ON

Read only

Process

0013

OUT2_IND

When the OUT2 control output is SCR 
(4-20mA) in Heating / Cooling type, 
it shows the temperature controller 
"OUT2 indicator" status. 

Read only

Process

0014

H1CM

Current measurement value of the 
heater break alarm output

Read only

Process

0016

ADESTS

Current situation of the AD error.
0001: AD conversion error

Read only

Process

0017

ERRSTS

Current situation of the input error.
0001:Input sensor Burn-out
0002: RJC error
0004: Input range exceeded
0008: Less than input range

Read only

Process

0018

AT_STS

Autotuning (AT) current state
0000: AT type
9999: AT in progress ("AT indicator" in 
the temperature controller front display 
blinking)

Read only

Process

0102

ZONE

Zone function set (For the zone position 
setting, set in RP parameter of each PID group 

0: OFF, 1: ON

Control Group

0104

ARW

ARW (Anti-reset windup) setting

0: AUTO, 50.0 ~ 200.0 %

*2 Control Group

0106

DI.SL

External contact input (DI) function

0: OFF, 1: ON

Control Group

0107

ALPHA Alpha factor of 2 DOF PID

0 ~ 100 %

Control Group

0108

UP.RT

Ramp-up temperature setting 

0: OFF / EUS(0~100 %) *1

Control Group

0109

DN.RT

Ramp-down temperature setting 

0: OFF / EUS(0~100 %) *1

Control Group

0110

RTMU

Ramp-time unit setting 

0: Hour, 1: Min

Control Group

0111

UPTM

Ramp-up time setting

0.01 ~ 99.59 [hh.mm]

*2 Control Group

0112

DNTM

Ramp-down time setting 

0.01 ~ 99.59 [hh.mm]

*2 Control Group

0113

RAMPT Ramp type selection

0: A Type, 1: B Type

Control Group

0120

MVMOD

Manual output function (when selecting 
the manual output, the "AT indicator" in the 
temperature controller front display is steady)

0: AUTO ,
1: MANUAL

Control Group

0121

MANMV Manual output value (Manual MV) set 0 ~ 100 %

Control Group

0122

CTRM

Control mode selection

0: Traditional,
1:2 2 DOF PID (2DOF)

Control Group

0124

HKSL

Hot-key selection

0: Auto-tuning (AT) function
1: Manual output function

Control Group

0300

SVNO

Set value (SV) number selection

1 ~ 3

Set value setting group

0301

SV1

Set value 1 (SV) setting

EU(0 ~ 100 %)

*1

Set value setting group

0302

SV2

Set value 2 (SV) setting

EU(0 ~ 100 %)

*1

Set value setting group

0303

SV3

Set value 3 (SV) setting

EU(0 ~ 100 %)

*1

Set value setting group

0305

AT MODE Auto-tuning (AT) type selection

0: Standard Automatic Operation
1: Low value (PV) type 
automatic operation

Auto-tuning Group

0306

AT

Auto-tuning (AT)

0: OFF, 1 ~ 4

Auto-tuning Group

0310

1.P

PID group 1 proportional band

0.0 ~ 999.9 %

*2

PID Group

0311

1.I

PID group 1 integral time

0 ~ 6000 sec

PID Group

0312

1.D

PID group 1 derivative time

0 ~ 6000 sec

PID Group

0313

1.MR

PID group 1 manual reset

-5.0 ~ 105.0 %

*2

PID Group

0314

1.PC

PID group 1 cooling proportional band 0.0 ~ 999.9 %

*2

PID Group

0315

1.IC

PID group 1 cooling integral time

0 ~ 6000 sec

PID Group

0316

1.DC

PID group 1 cooling derivative time

0 ~ 6000 sec

PID Group

0317

1.DB

PID group 1 Heating / Cooling dead band -100.0 ~ 50.0 %

*2

PID Group

0318

1.RP

PID group 1 zone position setting

EU(0 ~ 100 %), (1.RP < 2.RP) *1

PID Group

0320

2.P

PID group 2 proportional band

0.0 ~ 999.9 %

*2

PID Group

0321

2.I

PID group 2 integral time

0 ~ 6000 sec

PID Group

0322

2.D

PID group 2 derivative time

0 ~ 6000 sec

PID Group

0323

2.MR

PID group 2 manual reset

-5.0 ~ 105.0 % 

*2

PID Group

0324

2.PC

PID group 2 cooling proportional band 0.0 ~ 999.9 % 

*2

PID Group

0325

2.IC

PID group 2 cooling integral time

0 ~ 6000 sec

PID Group

0326

2.DC

PID group 2 cooling derivative time

0 ~ 6000 sec

PID Group

0327

2.DB

PID group 2 Heating / Cooling dead band -100.0 ~ 50.0 % 

*2

PID Group

0328

2.RP

PID group 2 zone position setting

EU(0 ~ 100 %), (1.RP < 2.RP) *1

PID Group

0330

3.P

PID group 3 proportional band

0.0 ~ 999.9 % 

*2

PID Group

0331

3.I

PID group 3 integral time

0 ~ 6000 sec

PID Group

0332

3.D

PID group 3 derivative time

0 ~ 6000 sec

PID Group

0333

3.MR

PID group 3 manual reset

-5.0 ~ 105.0 % 

*2

PID Group

D-register 

address

Parameter 

name

Parameter meaning

Parameter setting

Parameter 

division

0334

3.PC

PID group 3 cooling proportional band 0.0 ~ 999.9 % 

*2

PID Group

0335

3.IC

PID group 3 cooling integral time

0 ~ 6000 sec

PID Group

0336

3.DC

PID group 3 cooling derivative time

0 ~ 6000 sec

PID Group

0337

3.DB

PID group 3 Heating / Cooling dead 
band

-100.0 ~ 50.0 %

*2

PID Group

0400

HBA

Heater break alarm (HBA) current set 0: OFF, 1 ~ 50 A

Heater break 

alarm group

0401

HDB

Heater break alarm (HBA) Hysteresis
(deadband) set.

0 ~ 50

Heater break 

alarm group

0410

A1TY

Alarm 1 type setting

0: OFF, 1 ~ 21

Alarm Group

0411

A2TY

Alarm 2 type setting

0: OFF, 1 ~ 21

Alarm Group

0413

A1DB

Hysteresis (dead band) of alarm 1

EUS(0 ~ 100 %)

Alarm Group

0414

A2DB

Hysteresis (dead band) of alarm 2

EUS(0 ~ 100 %)

Alarm Group

0416

AL-1

Set value of alarm 1

PV alarm: EU (-100 ~ 100 %)
Deviation alarm: EUS (-100 ~ 100 %)

*1 Alarm Group

0417

AL-2

Set value of alarm 2

Alarm Group

0500

RET

Retransmission output type selection

0: Indicated value
1: Set value (SV)
2: Control output value (MV)
3: Power SPS for the sensor

Retransmission

group

0501

RET.H

Retransmission output upper limit setting -1999 ~ 9999

Retransmission

group

0502

RET.L

Retransmission output lower limit setting -1999 ~ 9999

Retransmission

group

0503

RET.T

Retransmission output form

0: 4 - 20 mA, 1: 0 - 20 mA

Retransmission

group

0600

OUT

Output type selection

0~12 (refer to the number of 
control output type selection)

Output group

0601

o.ACT

Output operation selection

0: Reverse operation (heating), 
1: Direct action (cooling)

Output group

0602

CT

Cycle type (Control cycle)

1 ~ 1000 sec

Output group

0603

CTC

Cooling cycle type (cooling control cycle) 1 ~ 1000 sec

Output group

0604

HYS

General type. ON/OFF control hysteresis Standard type,EUS(0~100%) *1

Output group

Heating / Cooling type. 
ON/OFF control hysteresis

Heating / Cooling type
0 ~ 10.0%

*2

0605

PO

Output1 setting when input breaks

-5.0~105.0% 

*2 Output group

0606

POC

Output2 setting when input breaks

0~105.0% 

*2 Output group

0607

OL-H

Output upper limit function

Standard type, 
OL-L +1 digit ~ 105.0 %
Heating / Cooling type,
0.0 ~ 105.0 %

*2

Output group

0608

OL-L

Output lower limit function

Standard type,  
-0.5 % ~ OL-H-1 digit
Heating / Cooling type,
0.0 ~ 105.0 %

*2

Output group

0610

INP

Input type selection

1~31

Input group

0611

UNIT

Temperature unit selection

0: ℃, 1: ℉

Input group

0612

FR-H

Upper range selection

EU(0 ~ 100 %)

*1 Input group

0613

FR-L

Lower range selection

EU(0 ~ 100 %)

*1 Input group

0614

DP-P

Decimal point position selection 
during the voltage input)

0: No decimal points
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places

Input group

0615

SL-H

Scale upper limit setting 
(during voltage input)

-1999 ~ 9999

Input group

0616

SL-L

Scale lower limit setting 
(during voltage input)

-1999 ~ 9999

Input group

0617

FILT

Measurement value filter selection

0: OFF, 1 ~ 120 sec

Input group

0618

BIAS

Measurement value correction setting EUS(-100 ~ 100%)

*1 Input group

0619

B.OUT

Operation selection when input breaks 0: OFF, 1: UP, 2: DOWN

Input group

0624

HYST

Hysteresis type

0: CENTER , 
1: EDGE 

Output group

*1: Please check the presence or absence of the decimal points according to the 
    input type and range settings

   · Set value with decimal points : if you want to input an SV1 of 100.0℃ through
     communication, transmit 03E8(100). (03E8 is the hex value of 1000) 
   · Set value without decimal points: if you want to input an SV1 of 100℃ through  
     communication, transmit 0064(100). (0064 is the hex value 100) 
*2 : Set value with decimal places. 

※  For the instructions of the protocol regarding communication, please refer to the 
Hanyoung protocol  instruction manual on Hanyoung Nux homepage(www.hynux.com).

How to dismantle case

● HX4

● HX3

● HX2

● HX7

● HX9

Содержание HX4

Страница 1: ... it is not possible please use shielded wires for the input signal wires For thermocouple TC please use ungrounded sensors There is a possibility of malfunction of the product by electric leakage if a grounded sensor is used If there is a lot of noise from the power line installing an insulated transformer or a noise filter is recommended The noise filter should be grounded on the panel and the wi...

Страница 2: ...99 9 4 E 1 100 0 999 9 5 T 1 199 9 400 0 6 R 0 1700 7 B 2 0 1800 8 S 0 1700 9 L 1 100 0 900 0 10 N 200 1300 1 0 of FS 1 Digit 11 U 1 199 9 400 0 0 5 of FS 1 Digit 12 W 0 2300 13 Platinel II 0 1390 Resistance temperature detector RTD 20 KPt100 Ω 3 199 9 500 0 0 5 of FS 1 Digit 21 Pt100 Ω 3 199 9 640 0 22 Pt100 Ω 3 200 640 DC voltage VDC DC 30 1 000 5 000 V DC 1999 9999 Scaling function SL H SL L ne...

Страница 3: ...ns for PID mode ANTI RESET WIND UP setting Auto 50 0 200 0 PID control 100 PID group setting 0 1 3 Always on 0 n Proportional band P 0 1 H C TYPE 0 0 999 9 Selecting one of PID groups 5 0 n Integral time I OFF 1 6000 s Always on 240 s n Derivative time D OFF 1 6000 s Always on 60 s n Manual reset 5 0 105 0 Integral time OFF 50 0 n Proportional band PC for cooling 0 0 ON OFF 0 1 999 9 heating cooli...

Страница 4: ...NC Hold 21 Heater break alarm 1 HBA1 Meaning of auto tuning AT start in auto tuning Group G At is as follows 1 is auto tuning for SV1 2 is auto tuning for SV2 3 is auto tuning for SV3 AUTO proceed with the Auto tuning in the order of the SV1 SV2 SV3 Function Description Function 1 Auto tuning Auto tuning is a function that the controller automatically measures the characteristics of the target sys...

Страница 5: ...t up low alarm is active when temperature is rising with power ON If you select alarm hold function there is no limit alarm ON during the temperature rise until set point Note If you want to use the alarm hold function please set proper parameter referring to alarm group G ALM Function 4 Ramp function Ramp function Type A Select A in Ramp function type rMP t parameters of control group G CtL The r...

Страница 6: ...u 3 Press SET key for 3 sec to go back to operation screen Function 15 HOT key This function is for activating deactivating most frequently used function on operation screen 1 Press SET UP key for 3 sec to activate hot key function 2 Press SET UP key for 3 sec again to deactivate hot key function One of the following two functions can be assigned as hot key function from the hot key select menu HK...

Страница 7: ...ime 0 6000 sec PID Group 0323 2 MR PID group 2 manual reset 5 0 105 0 2 PID Group 0324 2 PC PID group 2 cooling proportional band 0 0 999 9 2 PID Group 0325 2 IC PID group 2 cooling integral time 0 6000 sec PID Group 0326 2 DC PID group 2 cooling derivative time 0 6000 sec PID Group 0327 2 DB PID group 2 Heating Cooling dead band 100 0 50 0 2 PID Group 0328 2 RP PID group 2 zone position setting E...

Страница 8: ...SG RTD OUT REL 1 2 3 4 5 7 8 10 11 12 9 6 SV2 SV3 OUT1 SSR SCR RET OUT2 SSR SCR RET POWER 100 240 V 50 60 H 7 8 9 10 1 2 3 4 5 11 6 12 13 14 15 16 17 18 OUT1 RTX RTX OUT1 SSR SCR RET CT SV2 OUT2 SSR SCR RET POWER 100 240 V 50 60 Hz 5 5 VA A AL1 AL2 B B TC 11 12 Current Voltage CT SV3 HX9 HX3 HX4 HX7 HX2 OUT1 RELAY AL1 AL2 13 14 15 16 1 2 3 4 5 7 8 10 11 12 22 23 24 9 19 20 21 17 6 18 A B B SV2 TC ...

Отзывы: