█  External Contact Input (DI) Selection

3 predetermined set values (temperature values) could be changed with using 
ON/OFF of the external 2 contact inputs

Model

Code

Description

HX

☐ -

☐ Multi-input and output digital temperature controller

Dimension

2

48(W) × 96(H) ㎜

PID Auto-tuning

3

96(W) × 48(H) ㎜

4

48(W) × 48(H) ㎜

7

72(W) × 72(H) ㎜

9

96(W) × 96(H) ㎜

Control output  

0

Standard

1

Heating / Cooling (simultaneous control)

HX2/3/9 option

0 None

1

RS485 communi Heater break alarm (HBA)

HX7 option

0 None

1

RS485 communi DI 2 contacts (SV2, SV3)

2

RS485 communi Heater break alarm (HBA)

HX4 option

0 None

1

RS485 communi DI 1 contact (SV2)

2

RS485 communi Heater break alarm (HBA)

1381-3, Juan-Dong, Nam-Gu Incheon, Korea,  
TEL:(82-32)876-4697  FAX:(82-32)876-4696  http://www.hynux.com

HANYOUNGNUX CO.,LTD

HEAD OFFICE

Suffix code

Part name and function

Safety information

Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality.

•Please install an appropriate protective circuit on the outside. Malfunction or an incorrect operation may be 
   a cause of leading to a serious accident.
•Since this product does not have the power switch or a fuse, please install those separately on the outside. (Fuse rating : 250 V 0.5 A)
•To prevent damage or failure of this product, please supply the rated power voltage.
•To prevent electric shock or equipment failure, please do not turn on the power until completing wiring.
•Since this is not explosion-proof structure, please do not use in a place where combustible or explosive gas is around.
•Never disassemble, modify or repair the product. There is a possibility of malfunction, electric shock or a risk of fire.
•Please turn off the power when mounting/dismounting of the product.This is a cause of electric shock, malfunction, or failure.
•If the product is used with methods other than specified by the manufacturer, it may lead to injury or property damage.
•Since there is a possibility of electric shock, please use the product as mounted on a panel while the power is being supplied.
•If it is used with systems, machines and equipment that could lead to a risk of life or property damage, please 
   implement safety devices and protections for both lives and the applications and plan for preventing accidents.

Warning

Do not touch or connect any undesirable conductive part to input-output terminal, 
since there is a possibility of electric shock.

Danger

•The contents of the instruction manual are subjective to change without prior notice.
•Please make sure that the specification is the same as exactly you have ordered.
•Please make sure that the product is not damaged during shipping.
•Please use this product in a place where the ambient operating temperature is 0 ~ 50 ℃ (40 ℃ max, closely installed)  
   and the ambient operating humidity is 35 ~ 85 % R.H (without condensation).
•Please use this product in a place where corrosive gas (such as harmful gas, ammonia, etc.) 
   and flammable gas do not exist.
•Please use this product in a place where there is no direct vibration and a large physical impact to the product.
•Please use this product in a place where there is no water, oil, chemicals, steam, dust, salt, iron or 
   hazardous substances (Contamination class 1 or 2).
•Please do not wipe this product with organic solvents such as alcohol, 
   benzene or others. (Please use mild detergent instead)
•Please avoid places where excessive amount of inductive interference and electrostatic or magnetic noise occurs.
•Please avoid places where heat accumulation occurs due to direct sunlight or radiant heat.
•Please use this product in a place where the elevation is below 2,000 m.
•Please make sure to inspect the product if exposed to water, since there is a possibility of electric leakage or a risk of fire.
•For thermocouple (TC) input, please use a prescribed compensation lead wire. (There will be a temperature error if a general lead is used.)
•For resistance temperature detector (RTD) input, please use a small resistance of lead wire and the 3 lead wires should  
   have the same resistance. (There will be a temperature error if the 3 lead wires do not have the same resistance.)
•Please keep the input signal wire away from the power lines and load lines to avoid the effect of inductive noise.
•The input signal wires and output signal wires should be separated from each other. 
   If it is not possible, please use shielded wires for the input signal wires.
•For thermocouple (TC), please use ungrounded sensors. (There is a possibility of  
   malfunction of the product by electric leakage, if a grounded sensor is used.)
•If there is a lot of noise from the power line, installing an insulated transformer or a noise filter 
   is recommended. The noise filter should be grounded on the panel and the wire between 
   the output of the noise filter and the power of the instrument should be as short as possible.
•It is effective against noise, if the power lines of the product are made twisted pair wiring.
•Please make sure the operation of the product before using, since the product may not 
  operate as it intends to if the alarm function is not properly set.
•While replacing the sensor, please turn off the power.
•In case of the high frequent operation, such as proportional operation, please use an auxiliary 
  relay since the life span of the output relay will be shortened if it connects to the load without 
  the rated margin. In this case, SSR output is recommended.
 

*For Electromagnetic switch : set cycle time : minimum 20 sec.

 

*For SSR                         : set cycle time : minimum  1 sec.

•Please do not connect anything to the unused terminals.
•Please connect wires properly after making sure the polarity of the terminals.
•Please use a switch or breaker (IEC60947-1 or IEC60947-3 approved) 
  when the product is mounted on a panel.
•Please install a switch or break near the operator to facilitate its operation.
•If a switch or breaker is installed, please put a name plate that the power is off when the switch or breaker is activated. 
•In order to use this product properly and safely, we recommend periodic maintenance.
•Some parts of this product have limited expected life span and aged deterioration.
•The warranty of this product (including accessories) is 
   1 year only when it is used for the purpose it was intended to under normal condition.
•When the power is being supplied there should be a preparation time for the contact output. Please 
   use a delay relay together when it is used as a signal on the outside of interlock circuit or others.
•When the user replaces with a spare unit due to product failure or other reason, 
   please check the compatibility   since the operation can be varied by 
   the difference of setting parameters even though the model name and code are the same.
•Before using a temperature controller, there could be a temperature difference between 
   PV of the temperature controller and the actual temperature, so please operate the temperature 
   controller after correcting the temperature difference appropriately.

CAUTION

DANGER indicates an imminently hazardous situation which, 
if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, 
if not avoided, could result in death or serious injury.

CAUTION indicates a potentially hazardous situation which, 
if not avoided, may result in minor or moderate injury.

DANGER

WARNING

CAUTION

Number

Name

Description

Process value (PV) Displays the process value in the operation mode.

Set value (SV)

Displays the set value in the operation mode.

Up key

Increases the set value or used to move between groups and 
to change an option in a parameter in setting mode.

Down 

key

Decreases the set value or used to move between groups and 
to change an option in a parameter in setting mode.

Shift key Used to move the position of the digit.

Set key

Sets (confirm) the set value, displays the output amount, or set an 

option in a parameter in setting mode and moves between the 

parameters in a group. By pressing for 3 seconds, it enters the 

display setting mode (setting mode) or returns to the operation mode.

Operation

Indicator

Lights when SV2 is displayed.
Lights when SV3 is displayed.
OUT1 indicator.
OUT2 indicator.
Auto-tuning indicator (blink).
Alarm 1 operation indicator.
Alarm 2 operation indicator.

⑧      +

Hot 

key(run/

stop)

Hot key is designated for AT or Manual MV 
configuable in the group of "G.CtL"

⑨      +

Quick 
menu

Sets the value: SV1, SV2, AL1, AL2

External input

contact

selection

(             )

OFF (contact input is not used)

ON (contact input is used)

No display

External contact input

SV2

SV3

Set value 1 display (SV1)

OFF

OFF

Set value 2 display (SV2)

ON

OFF

Set value 3 display (SV3)

OFF

ON

Thank you for purchasing HANYOUNG product.
Please check whether the product is exactly the same as you ordered. 
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time.

 INSTRUCTION MANUAL

HX 

series

 

  

Digital Temperature Controller

Содержание HX4

Страница 1: ... it is not possible please use shielded wires for the input signal wires For thermocouple TC please use ungrounded sensors There is a possibility of malfunction of the product by electric leakage if a grounded sensor is used If there is a lot of noise from the power line installing an insulated transformer or a noise filter is recommended The noise filter should be grounded on the panel and the wi...

Страница 2: ...99 9 4 E 1 100 0 999 9 5 T 1 199 9 400 0 6 R 0 1700 7 B 2 0 1800 8 S 0 1700 9 L 1 100 0 900 0 10 N 200 1300 1 0 of FS 1 Digit 11 U 1 199 9 400 0 0 5 of FS 1 Digit 12 W 0 2300 13 Platinel II 0 1390 Resistance temperature detector RTD 20 KPt100 Ω 3 199 9 500 0 0 5 of FS 1 Digit 21 Pt100 Ω 3 199 9 640 0 22 Pt100 Ω 3 200 640 DC voltage VDC DC 30 1 000 5 000 V DC 1999 9999 Scaling function SL H SL L ne...

Страница 3: ...ns for PID mode ANTI RESET WIND UP setting Auto 50 0 200 0 PID control 100 PID group setting 0 1 3 Always on 0 n Proportional band P 0 1 H C TYPE 0 0 999 9 Selecting one of PID groups 5 0 n Integral time I OFF 1 6000 s Always on 240 s n Derivative time D OFF 1 6000 s Always on 60 s n Manual reset 5 0 105 0 Integral time OFF 50 0 n Proportional band PC for cooling 0 0 ON OFF 0 1 999 9 heating cooli...

Страница 4: ...NC Hold 21 Heater break alarm 1 HBA1 Meaning of auto tuning AT start in auto tuning Group G At is as follows 1 is auto tuning for SV1 2 is auto tuning for SV2 3 is auto tuning for SV3 AUTO proceed with the Auto tuning in the order of the SV1 SV2 SV3 Function Description Function 1 Auto tuning Auto tuning is a function that the controller automatically measures the characteristics of the target sys...

Страница 5: ...t up low alarm is active when temperature is rising with power ON If you select alarm hold function there is no limit alarm ON during the temperature rise until set point Note If you want to use the alarm hold function please set proper parameter referring to alarm group G ALM Function 4 Ramp function Ramp function Type A Select A in Ramp function type rMP t parameters of control group G CtL The r...

Страница 6: ...u 3 Press SET key for 3 sec to go back to operation screen Function 15 HOT key This function is for activating deactivating most frequently used function on operation screen 1 Press SET UP key for 3 sec to activate hot key function 2 Press SET UP key for 3 sec again to deactivate hot key function One of the following two functions can be assigned as hot key function from the hot key select menu HK...

Страница 7: ...ime 0 6000 sec PID Group 0323 2 MR PID group 2 manual reset 5 0 105 0 2 PID Group 0324 2 PC PID group 2 cooling proportional band 0 0 999 9 2 PID Group 0325 2 IC PID group 2 cooling integral time 0 6000 sec PID Group 0326 2 DC PID group 2 cooling derivative time 0 6000 sec PID Group 0327 2 DB PID group 2 Heating Cooling dead band 100 0 50 0 2 PID Group 0328 2 RP PID group 2 zone position setting E...

Страница 8: ...SG RTD OUT REL 1 2 3 4 5 7 8 10 11 12 9 6 SV2 SV3 OUT1 SSR SCR RET OUT2 SSR SCR RET POWER 100 240 V 50 60 H 7 8 9 10 1 2 3 4 5 11 6 12 13 14 15 16 17 18 OUT1 RTX RTX OUT1 SSR SCR RET CT SV2 OUT2 SSR SCR RET POWER 100 240 V 50 60 Hz 5 5 VA A AL1 AL2 B B TC 11 12 Current Voltage CT SV3 HX9 HX3 HX4 HX7 HX2 OUT1 RELAY AL1 AL2 13 14 15 16 1 2 3 4 5 7 8 10 11 12 22 23 24 9 19 20 21 17 6 18 A B B SV2 TC ...