HANBAY Inc
User Manual RCx-xxxAS-1.05
Page 2 of 15
www.hanbayinc.com
Rev.2018.1
1 800 315 4461
The actuator comes standard with a Turck 6 position connector
and a 20’ cable with plug. Cut the cable to the
length required and then connect according to the following wire color schematic:
Wire color schematic for
“Turck6” cable:
Pin Colour
DC power supply only
6
White
+24VDC
5
Black
Power Gnd
4
Pink
TD(A)
3
Grey
TD(B)
2
Brown
Isolated
*
Input Signal Gnd
1
Blue
Isolated
*
Input + Signal (4..20mA)
Connect the power:
The
RCx
may be connected to voltages ranging from: 12
– 24 VDC.
18
VDC is required for full ‘Digital Potentiometer’ functionality (see pg. 7)
The power consumption will range from max. 3.0A to approx.. min. 100mA
when the actuator is active. When not moving, the actuator draws less
than 50mA.
Terminal
1 2 3 4 5 6
GND
V+
DC Voltages
1 2 3 4 5 6
P
1
Turck connector
not included in CSA
rated explosion
proof enclosures