             User Manual RCx-xxxAS-1.05 

Page 12 of 15 

www.hanbayinc.com                       

  

     

Rev.2018.1

 

1 800 315 4461 

 

[email protected]

       

Alternative method to read the “

S

tatusRegister”

 

Bits in “StatusRegister” can be read independently by using function code 2.  

In the PDU Discrete Inputs are 

addressed starting at zero. Therefore Discrete Inputs numbered 1-5 are addressed as 0-4. 
 

Example 1: 

 

To read all of the discrete inputs in actuator number 33, the master needs to send 

Actuator 

address 

Function 

code 

Input 

address 

Qty of 
inputs 

CRC 

0x21 

0x02 

0x0000 

0x0005 

0x---- 

1 byte 

1 byte 

2 bytes 

2 bytes 

2 bytes 

 

Example 2:

  

To read the discrete inputs 1 and 2 (Opened and Closed) in actuator number 33, the master needs to 

send

 

Actuator 

address 

Function 

code 

Input 

address 

Qty of 
inputs 

CRC 

0x21 

0x02 

0x0000 

0x0002 

0x---- 

1 byte 

1 byte 

2 bytes 

2 bytes 

2 bytes 

 

Example 2:  

To read the discrete inputs 4 (Stalled closed) in actuator number 33, the master needs to send

 

Actuator 

address 

Function 

code 

Input 

address 

Qty of 
inputs 

CRC 

0x21 

0x02 

0x0003 

0x0001 

0x---- 

1 byte 

1 byte 

2 bytes 

2 bytes 

2 bytes 

 
 
 

Register name 

Address 

Max 

Min 

Default 

 

Actuator 
address 

Function 
code 

CRC 

N/A

 

0x0064 

N/A 

N/A 

N/A 

Example:

  Re-zero actuator number 1

 

0x01 

0x64 

0x---- 

1 byte 

1 byte 

2 bytes 

 
 
 

Register name 

Address 

Max 

Min 

Default 

 

Actuator 
address 

Function 
code 

CRC 

N/A

 

0x0065 

N/A 

N/A 

N/A 

Example:

  Close the valve on actuator number 1

 

0x01 

0x65 

0x---- 

1 byte 

1 byte 

2 bytes 

 
 
 

Register name 

Address 

Max 

Min 

Default 

 

Actuator 
address 

Function 
code 

CRC 

N/A

 

0x0066 

N/A 

N/A 

N/A 

Example:

  Open the valve on actuator number 1

 

0x01 

0x66 

0x---- 

1 byte 

1 byte 

2 bytes 

 
 
 
 
 
 
 
 

Содержание RC AS-1.05 Series

Страница 1: ...s pg 3 Operation pg 4 6 DIP Switch pg 4 Recalibration pg 4 Troubleshooting pg 4 Communications parameters pg 5 Speed and Torque details pg 5 6 Appendix pg 7 14 Modbus Protocol pg 7 12 Power settings p...

Страница 2: ...ower supply only 6 White 24VDC 5 Black Power Gnd 4 Pink TD A 3 Grey TD B 2 Brown Isolated Input Signal Gnd 1 Blue Isolated Input Signal 4 20mA Connect the power The RCx may be connected to voltages ra...

Страница 3: ...the picture above then connect your input signal on pos 3 and 4 as shown below ACTUATOR 1 2 3 4 5 6 P2 4 20mA Signal source user powered TD A TD B SIGNAL GND RCx Internal RES R66 NOTE 1 Usually the ac...

Страница 4: ...it one second and then put it back or use the command code 0x64 In both cases you will see the actuator closing the valve very slowly Troubleshooting Upon noticing a problem your first step should alm...

Страница 5: ...only limit the maximum speed The faster you set this maximum speed the less torque you can expect at this maximum speed as shown in the tables below NOTE Depending ONLY on the power setting address 0x...

Страница 6: ...que values are for valve seating 2 30 3 18 To convert in lbs to Nm divide the in lbs value by 9 Speed and Torque of RCF xxxAS Actuators Maximum Speed Address 0x0000 Time for 1 Turn sec Torque in in lb...

Страница 7: ...isters READ and WRITE 1 0x0001 4002 MaximumPower 2 0x0002 4003 NumberOfTurns 3 0x0003 4004 TargetFromRS485Flag 4 0x0004 4005 InputRangeLow 5 0x0005 4006 InputRangeHigh 6 0x0006 4007 OutputRangeLow 7 0...

Страница 8: ...em when in the seating mode The actuator will try to reach the speed set by MaximumSpeed If the torque required is too high the actuator will automatically slow down and deliver the maximum available...

Страница 9: ...000 in actuator number 23 0x17 0x06 0x0005 0xFDE8 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes For a detailed explanation of this two registers please see TargetPosition register description Register name...

Страница 10: ...valve 5 turns TargetPosition register has to be set to 1500 Register name Address Max Min Def Actuator address Function code Register address Register new value CRC SignalLostPosition 0x0009 InputRan...

Страница 11: ...ngeLow 0 OutputRangeHigh 10000 If CurrentPosition equals to 10000 that means the valve is 5 turns opened If CurrentPosition equals to 2000 that means the valve is 1 turns opened Example 2 If the actua...

Страница 12: ...to send Actuator address Function code Input address Qty of inputs CRC 0x21 0x02 0x0000 0x0002 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes Example 2 To read the discrete inputs 4 Stalled closed in actua...

Страница 13: ...2 0 0 1 1 0 0 13 0 0 1 1 0 1 14 0 0 1 1 1 0 15 0 0 1 1 1 1 16 0 1 0 0 0 0 17 0 1 0 0 0 1 18 0 1 0 0 1 0 19 0 1 0 0 1 1 20 0 1 0 1 0 0 21 0 1 0 1 0 1 22 0 1 0 1 1 0 23 0 1 0 1 1 1 24 0 1 1 0 0 0 25 0 1...

Страница 14: ...nbayinc com Rev 2018 1 1 800 315 4461 hanbaysales hanbayinc com Main Dimensions Desiccant sticks These sticks change colour when exposed to moisture When they change from the original colour blue to p...

Страница 15: ...HANBAY Inc User Manual RCx xxxAS 1 05 Page 15 of 15 www hanbayinc com Rev 2018 1 1 800 315 4461 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number...

Отзывы: