Operation 

 

 

DIP switches: 

 

The DIP switches allow you to change the  
settings on your actuator. To flip a switch, 
gently use a small flat-head screwdriver. 
See chart on next page for DIP switch functionality. 

 
 
 
 
 

 

 

 

 

 

        

 

 

Direction of rotation:  

 
To change the direction of rotation, turn off the actuator, change the position of switch DIP 12 and power it up again.

 

 

 

Calibration: 

 

The  actuator  will  re-zero  when  the  input  signal  is  between  2.8  and  4.16mA  (0.700V 

–  1.040V).  It  will  turn  either 

clockwise or anti-clockwise (depending on direction selection of DIP 12) until the actuator has reached the fully closed 
position of the valve.  

 
If you need to re-zero the actuator because you have changed the valve, 

while the actuator is on, toggle DIP12 

wait one second and then put it back or use the command code 0x64. In both cases you will see the actuator closing 
the valve very slowly. 
 
 

 
 
 

 
 
Troubleshooting: 

 
Upon noticing a problem, your first step should almost always be to recalibrate the actuator by switching DIP 12, 
then switching it back to its original position, all while the actuator is powered. This alone can solve basic problems. 
See section 3 on this page for more details. 
 

If the actuator does not move, try following these steps:  

1) 

Re-calibrate the actuator. This will move the actuator regardless of what signal it is receiving.  

2) 

A sticking valve may be the problem. Remove the valve from the actuator, and re-test the actuator.   

3) 

Remove power. Re-check the wiring and the power/signal apparatus. Power actuator, and re-calibrate.       
If the problem persists, please call Hanbay for technical support. 

 

 

 

DIP switches. In this example DIPs 1, 2, 6 and 12 are on. 

 
It is VERY important that you put back DIP12.  If you do not that, the actuator will turn in the opposite direction 
next time you power it up. 

Содержание RC AS-1.05 Series

Страница 1: ...s pg 3 Operation pg 4 6 DIP Switch pg 4 Recalibration pg 4 Troubleshooting pg 4 Communications parameters pg 5 Speed and Torque details pg 5 6 Appendix pg 7 14 Modbus Protocol pg 7 12 Power settings p...

Страница 2: ...ower supply only 6 White 24VDC 5 Black Power Gnd 4 Pink TD A 3 Grey TD B 2 Brown Isolated Input Signal Gnd 1 Blue Isolated Input Signal 4 20mA Connect the power The RCx may be connected to voltages ra...

Страница 3: ...the picture above then connect your input signal on pos 3 and 4 as shown below ACTUATOR 1 2 3 4 5 6 P2 4 20mA Signal source user powered TD A TD B SIGNAL GND RCx Internal RES R66 NOTE 1 Usually the ac...

Страница 4: ...it one second and then put it back or use the command code 0x64 In both cases you will see the actuator closing the valve very slowly Troubleshooting Upon noticing a problem your first step should alm...

Страница 5: ...only limit the maximum speed The faster you set this maximum speed the less torque you can expect at this maximum speed as shown in the tables below NOTE Depending ONLY on the power setting address 0x...

Страница 6: ...que values are for valve seating 2 30 3 18 To convert in lbs to Nm divide the in lbs value by 9 Speed and Torque of RCF xxxAS Actuators Maximum Speed Address 0x0000 Time for 1 Turn sec Torque in in lb...

Страница 7: ...isters READ and WRITE 1 0x0001 4002 MaximumPower 2 0x0002 4003 NumberOfTurns 3 0x0003 4004 TargetFromRS485Flag 4 0x0004 4005 InputRangeLow 5 0x0005 4006 InputRangeHigh 6 0x0006 4007 OutputRangeLow 7 0...

Страница 8: ...em when in the seating mode The actuator will try to reach the speed set by MaximumSpeed If the torque required is too high the actuator will automatically slow down and deliver the maximum available...

Страница 9: ...000 in actuator number 23 0x17 0x06 0x0005 0xFDE8 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes For a detailed explanation of this two registers please see TargetPosition register description Register name...

Страница 10: ...valve 5 turns TargetPosition register has to be set to 1500 Register name Address Max Min Def Actuator address Function code Register address Register new value CRC SignalLostPosition 0x0009 InputRan...

Страница 11: ...ngeLow 0 OutputRangeHigh 10000 If CurrentPosition equals to 10000 that means the valve is 5 turns opened If CurrentPosition equals to 2000 that means the valve is 1 turns opened Example 2 If the actua...

Страница 12: ...to send Actuator address Function code Input address Qty of inputs CRC 0x21 0x02 0x0000 0x0002 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes Example 2 To read the discrete inputs 4 Stalled closed in actua...

Страница 13: ...2 0 0 1 1 0 0 13 0 0 1 1 0 1 14 0 0 1 1 1 0 15 0 0 1 1 1 1 16 0 1 0 0 0 0 17 0 1 0 0 0 1 18 0 1 0 0 1 0 19 0 1 0 0 1 1 20 0 1 0 1 0 0 21 0 1 0 1 0 1 22 0 1 0 1 1 0 23 0 1 0 1 1 1 24 0 1 1 0 0 0 25 0 1...

Страница 14: ...nbayinc com Rev 2018 1 1 800 315 4461 hanbaysales hanbayinc com Main Dimensions Desiccant sticks These sticks change colour when exposed to moisture When they change from the original colour blue to p...

Страница 15: ...HANBAY Inc User Manual RCx xxxAS 1 05 Page 15 of 15 www hanbayinc com Rev 2018 1 1 800 315 4461 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number...

Отзывы: