HAMWORTHY HEATING LTD
38
Merley Boiler Sequence Controller
500001210/D
DHW storage tank
5020
F
Flow setpoint boost
16
0
30
°C
5021
F
Increase of transfer boost
8
0
30
°C
5022
F
Type of charging
with B3 ¦ With B3 and B31 ¦ Legionella B3 and B31
With B3 and B31
5050
F
Charging temperature maximum
80
8
BZ 5051 OEM
°C
5060
F
Electric immersion heater operating mode
Substitute ¦ Summer ¦ Always
Substitute
-
5061
F
Electric immersion heater release
24h/day ¦ DHW release¦ Time program4/ DHW
DHW release
-
5062
F
Electric immersion heater control
External thermostat ¦ DHW sensor
DHW sensor
-
5085
F
Excess heat draw
Off ¦ On
On
-
5092
F
With primary controller / system pump
No ¦ Yes
No
5101
6)
F
Pump speed minimum
40
0
100
%
5102
6)
F
Pump speed maximum
100
0
100
%
Configuration
5710
I
Heating circuit 1
Off ¦ On
On
-
5730
I
DHW sensor B3
Sensor ¦ Thermostat
Sensor
-
5731
I
DHW control element Q3
None ¦ Charging pump ¦ Diverting valve
charging pump
-
5736
I
Separate DHW circuit
Off ¦ On
Off
-
5890
I
Relay output QX1
None ¦ Circulating pump Q4 ¦ Electric immersion heater
DHW K6 ¦ H1 pump Q15 ¦ Boiler pump Q1 ¦ Alarm output
K10 ¦ 2nd pump speed HC1 Q21 ¦ ¦ H pump Q18 ¦ System
pump Q14 ¦ Heat generator shutoff valve Y4 ¦Time
program 5 K13 ¦ H3 pump Q19 ¦ Flue gas relay K17 ¦
Assisted firing fan K30 ¦ Cascade pump Q25 ¦ DHW
mixing pump Q35 ¦ DHW internal circulating pump Q33 ¦
Heat request K27 ¦
None
-
°C
5891
6)
I
Relay output QX2
None ¦ Circulating pump Q4 ¦ Electric immersion heater
DHW K6 ¦ Collector pump Q5 ¦ H1 pump Q15 ¦ Boiler
pump Q1 ¦ Alarm output K10 ¦ 2nd pump speed HC1 Q21
¦ H pump Q18 ¦ System pump Q14 ¦ Heat generator
shutoff valve Y4 ¦Time program 5 K13 ¦ H3 pump Q19 ¦
Cascade pump Q25 ¦ DHW mixing pump Q35 ¦ DHW
internal circulating pump Q33 ¦ Heat request K27 ¦
None
-
95
5930
I
Sensor input BX1
None ¦ DHW sensor B31 ¦ Return sensor B7 ¦ DHW
circulation sensor B39 ¦ Common flow sensor B10
¦ DHW charging sensor B36 ¦ Common return sensor B73
¦ Cascade return sensor B70 ¦
None
-
°C
5950
I
Function of input H1
Operating mode changeover HCs + DHW ¦ Operating
mode changeover HCs ¦ Operating mode changeover
HC1 ¦ Heat generation lock ¦ Error/alarm message ¦
Minimum flow temperature setpoint ¦
Heat request 10V ¦ Room temperature 10V
Operating mode changeover
HCs+DHW
-
-
5951
I
Operating action of contact H1
NC ¦ NO
NO
-
5952
I
Minimum flow temperature setpoint H1
70
120
°C
8
5954
I
Temperature value 10V H1
100
130
°C
5
Op
er
ating
Lin
e
Us
e
r Le
vel
Fu
nction
De
fault
Va
lu
e
Max
imum
Min
imum
Unit