HAMWORTHY HEATING LTD
59
Merley Boiler Sequence Controller
500001210/D
Primary controller
Line no.
Operating line
HC1
872
With primary controller / system pump
With primary controller /
system pump
Specify whether the heating circuit receives its heat via the primary controller or with the
help of the system pump (depending on the type of plant).
Speed
-
controlled pump
Line no.
Operating line
HC1
882
Pump speed min
883
Pump speed max
Pump speed min
The minimum speed of the heating circuit pump can be defined
Pump speed max
The maximum speed of the heating circuit pump can be defined.
Remote control
Line no.
Operating line
HC1
900
Operating mode changeover
None ¦ Protection ¦ Reduced ¦
Comfort ¦ Automatic
In the case of external changeover via inputs H1 / H2 / H3, the
operating mode to be used can be selected.