HAMWORTHY HEATING LTD
36
Merley Boiler Sequence Controller
500001210/D
Time program heating circuit 1
500
E
Preselection
Mo
-
Su ¦ Mo
-
Fr ¦ Sa
-
Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
Mo
-
Su
-
501
E
1st phase on
6:00
0.00
24:00
hh:mm
502
E
1st phase off
22:00
0.00
24:00
hh:mm
503
E
2nd phase on
24:00
0.00
24:00
hh:mm
504
E
2nd phase off
24:00
0.00
24:00
hh:mm
505
E
3rd phase on
24:00
0.00
24:00
hh:mm
506
E
3rd phase off
24:00
0.00
24:00
hh:mm
516
E
Standard values
No ¦ Yes
No
-
Time program 4 / DHW
560
E
Preselection
Mo
-
Su ¦ Mo
-
Fr ¦ Sa
-
Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
Mo
-
Su
-
561
E
1st phase on
6:00
00:00
24:00
hh:mm
562
E
1st phase off
22:00
00:00
24:00
hh:mm
563
E
2nd phase on
24:00
00:00
24:00
hh:mm
564
E
2nd phase off
24:00
00:00
24:00
hh:mm
565
E
3rd phase on
24:00
00:00
24:00
hh:mm
566
E
3rd phase off
24:00
00:00
24:00
hh:mm
576
E
Standard values
No ¦ Yes
No
-
Holidays heating circuit 1
641
E
Preselection
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period 6¦
Period 7¦ Period 8
Period 1
-
642
E
Start
--
.
--
01.01
31.12
dd.mm
643
E
End
--
.
--
01.01
31.12
dd.mm
648
E
operating level
Frost protection ¦ Reduced
frost protection
-
Heating Circuit 1
710
E
Comfort cooling setpoint
20.0
Operating line 712
Operating line 716
°C
712
E
Reduced setpoint
16
Operating line 714
Operating line 710
°C
714
E
Frost protection setpoint
10.0
4
Operating line 712
°C
716
F
Comfort setpoint maximum
35.0
Operating line 710
35.0
°C
720
E
Heating curve slope
1.50
0.1
4.00
-
721
F
Heating curve displacement
0.0
-
4.5
4.5
°C
726
F
Heating curve adaption
Off ¦ On
-
Off
730
E
Summer/winter heating limit
18
---
/8
30
°C
732
F
24
-
hour heating limit
-
3
---
/
-
10
10
°C
740
I
Flow temperature setpoint minimum
8
8
Operating line 741
°C
741
I
Flow temperature setpoint maximum
80
Operating line 740
95
°C
750
F
Room influence
20
---
/1
100
%
760
F
Room temperature limitation
1
-
-
-
/ 0.5
4
°C
770
F
Boost heating
5
-
-
-
/ 0
20
°C
780
F
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost protection
setpoint
Down to reduced setpoint
-
Op
er
ating
Lin
e
Us
e
r Le
vel
Fu
nction
De
fault
Va
lu
e
Max
imum
Min
imum
Unit