HAMWORTHY HEATING LTD
45
Merley Boiler Sequence Controller
500001210/D
5.3.2 Programming
Settings
Used as
Direct adjustment
ru = 1 (factory setting)
The room unit is addressed as room unit 1
A long press on the presence button enables the service level to be accessed.
Configuration
P1 = 1 (factory setting)
Automatic storage:
A setpoint readjustment with the knob is adopt-
ed either by pressing the operating mode button
or without any further confirmation (timeout).
P1 = 2
Storage with confirmation:
A setpoint readjustment with the knob is adopt-
ed only after pressing the operating mode but-
ton.