
33
Hampton
®
H27U-NG/H27U-LP Direct Vent Freestanding Gas Stove
installation
Gas Pipe Pressure Testing
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1)
Make sure the valve is in the "OFF" position.
2)
Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide flat
screwdriver.
3)
Attach manometer to "IN" and/or "OUT" pres-
sure tap(s) using a 5/16" ID hose.
4)
Light the pilot and turn the valve to "ON" posi-
tion. Read manometer.
5)
The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6)
When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not over
tighten
Aeration Adjustment
The burner aeration is factory set but may need ad-
justing due to either the local gas supply, air supply
or altitude.
Natural Gas
3/16" (4.76 mm)
Propane
1/4" (6.4 mm)
The aeration adjustment rod is located on the right
lower side of the unit. Remove the small access
panel by removing 1 screw to access Aeration
Adjustment Rod - see below.
Push up to close or pull down to open.
Caution: Carbon will be produced if the air
shutter is closed too much.
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
Note: Aeration Adjustment should only be
performed by an authorized Hampton
®
Installer at the time of installation or
service.
Aeration Adjustment Wire
Valve Description
1)
Gas on/off knob
2)
Manual high/low adjustment
3)
Pilot Adjustment
4)
Thermocouple Connection
5)
Main Operator
6)
Outlet Pressure Tap (Manifold Pressure)
7)
Inlet Pressure Tap (Supply Pressure)
8)
Pilot Outlet
9)
Main Gas Outlet
10)
Flange Securing Screw Holes
11)
Alternative TC Connection Point
12)
Thermoelectric Unit
13)
Additional Valve Mounting Hole
Содержание H27U-NG
Страница 49: ...49 Hampton H27U NG H27U LP Direct Vent Freestanding Gas Stove notes...
Страница 54: ...54 Hampton H27U NG H27U LP Direct Vent Freestanding Gas Stove warranty...
Страница 55: ......