Capture Jet
®
with Water Wash Operation & Maintenance Manual
OM-0
06/1
120
16/re
v2/EN
EXHAUST AIRFLOWS
Please see submittal drawings or contact the manufacturer for each hood’s exhaust air flow rates. Halton’s applications
department determines the optimum exhaust rate for effective capture & containment of cooking effluent. These exhaust
airflows are included in the job submittal drawings for each hood and are customized for the specific kitchen appliance
arrangement and environment.
INSTALLATION INSTRUCTIONS
1. Inspect the crating carefully. If there are signs of damage, call the freight carrier before uncrating the units. Carefully
uncrate the units. Check all local codes prior to installation; special requirements may be necessary depending on
local building material construction.
** Important note ** Do not leave unit (s) exposed to extreme temperatures for an extended period of time, this
may cause the protective PVC coating around the unit (s) to become very difficult to remove.
2. Position the hood near the actual installation site. In case of multiple hoods, check the engineered set of drawings
for locations. Pay close attention to collar sizes and fire protection layouts, matching the hood systems to the correct
location shown on the drawings provided.
**Check item numbers on crates / hoods vs. drawing item numbers.
3. Once the hood is carefully removed from the shipping crate and set in position, the unit is now ready for installation.
If Halton Company has supplied a backsplash assembly, then the splash assembly should be installed first, for
installation procedures see pg. 6.
4. Hang the hood using ½” threaded rods by attaching the rods to the hood through the hanger brackets that are welded
to the top of the hood. Use of turnbuckles with the threaded rod sections will make final adjustment easier. Standard
hanging height for canopy hoods ranges from 78” min. to 84” max. from the finished floor to the lower edge of the
front of the hood (per local codes having jurisdiction). **Noted in installation details illustration- see pg. 7.
Note:
Allow 100lbs (45kg) per linear foot hanging weight.
Do not lift exhaust hoods from their end panels. Lift from four corners
All exhaust hoods and control panels are fitted together and factory tested prior to shipping for alignment and
operation.
5. Duct connections must meet NFPA 96 requirements and applicable local codes. Size of connection is indicated on
exhaust hood drawing. Connection is to be made after exhaust hood is hung.
6. Electrical circuits should be connected according to the job specific wiring diagram shown on the submittal drawings.
Water Wash hoods have additional wiring requirements to connect the control panel to the hoods, as well as
connections between multiple hoods operated from the same control panel. A typical field wiring diagram showing
these connections is shown on pg. 29. The following electrical service requirements are field installed:
A 120 volt, 15 amp uninterrupted supply to the control panel.
A separate 120 volt, 15 amp supply to the light fixture junction box(es) on top of each hood.
A 120 volt circuit from the control panel to the exhaust fan starter coil or relay.
Содержание Capture Jet KVE-WW
Страница 10: ...10 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN CLOSURE PANEL ASSEMBLY...
Страница 11: ...11 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...
Страница 12: ...12 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...
Страница 19: ...19 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...
Страница 26: ...26 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...
Страница 28: ...28 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN FIELD WIRING DIAGRAM...