GENERAL DESCRIPTION

Halton’s Water Wash technology provides solutions for a variety of commercial food service ventilation applications over 
virtually any cooking process. Based on Halton’s patented highly efficient Capture Jet

®

 solution and advanced mechanical 

KSA filter technology, the Water Wash feature keeps the plenum virtually grease free.  Halton’s Automatic Water Wash 
features allow for continuous operation without extended shut down for cleaning.  The hot water wash down is especially 
suited to facilities with cooking operation producing substantial volumes of grease and requires reduced maintenance. 
The Water Wash system includes three full length wash manifolds equipped with brass spray nozzles. These manifolds 
wash the exhaust plenum area and the KSA grease filters. When the wash cycle is initiated the exhaust fan shall shut off.  
The Water Wash system is built into the hood with complete controls and safety features.  The hood is complete with a 
control panel indicating the total hours of operation, safety alarms, security on, and exhaust fan failure.   

The control panel is connected to the electrical control box of the fan via a relay which detects any exhaust fan failures. 

To achieve the optimum performance from your hood system (s) please use the following guidelines provided within the 
pages of this Installation, Operation and Maintenance Manual.

In addition to this information technical support is available from the Halton Factory during regular office hours, 7 A.M. to 
5 P.M. Central Time, to provide support for products, applications, installation, commissioning or for any aspect that you 
may have.  Our local sales representatives can also provide support.

RECOMMENDATION

Upon receipt of the Halton hood (s), inspect unit (s) immediately for any shipping damage and notify carrier immediately 
if damage is found. Halton will not accept responsibility for any shipping damage. All systems are thoroughly inspected 
before leaving our factories; however Halton will assist in filing a claim if needed.

GENERAL INSTALLATION

It is the responsibility of the installing contractor to see that the system installation is completed in accordance with 
the project plans and specifications and that it meets all specific requirements of local code officials.  The local authority 
having jurisdiction could over rule some of the installation details written in this manual.  The installation shall be in 
accordance with NFPA-96. All electrical systems shall be installed following local and national codes.

The owner and/or operator should be instructed in the proper operation, care and maintenance of the system.

If questions or complications should arise during the installation of the Halton hood (s) that cannot be solved using the 
instructions provided please contact the Halton office at 1-800-442-5866, or (1-800-4-HALTON).

Note: There are no instructions contained within this manual for installation or maintenance of fan packages. 

**See appropriate manufacturers manual for detailed instructions.

Содержание Capture Jet KVE-WW

Страница 1: ...pture Jet Hoods with Water WashTechnology Manual provides Operation Maintenance and Service Instructions Form OM006_CAPTURE JET WITH WATER WASH Date 07 11 2016 Rev2 Capture Jet Hoods with Water WashTe...

Страница 2: ...ance Manual In addition to this information technical support is available from the Halton Factory during regular office hours 7 A M to 5 P M Central Time to provide support for products applications...

Страница 3: ...backsplash assembly then the splash assembly should be installed first for installation procedures see pg 6 4 Hang the hood using threaded rods by attaching the rods to the hood through the hanger br...

Страница 4: ...X 1 2 16 8 gallons per minute 2 Supply and connect 1 ips for hot water to control panel provide and connect 1 lines to ventilator sections Supply and connect drains as specified from ventilator secti...

Страница 5: ...5 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN Water Inlet point on back of hood Water Drain point on hood...

Страница 6: ...016 rev2 EN BACKSPLASH INSTALLATION Screw through top flange into wall Screw head will not interfere with hood Screw backsplash to wall or attached with adhesive Halton canopy hoods should be installe...

Страница 7: ...7 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN HOOD INSTALLATION DETAILS...

Страница 8: ...8 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN EXHAUST DUCT CONNECTION DETAILS...

Страница 9: ...9 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN SPLICE STRIP U CHANNEL ASSEMBLIES...

Страница 10: ...10 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN CLOSURE PANEL ASSEMBLY...

Страница 11: ...11 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...

Страница 12: ...12 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...

Страница 13: ...them clean The cap should be removed for taking the static pressure measurements and then replaced when the measurements are completed The exhaust static pressure is measured using the negative conne...

Страница 14: ...the removal and replacement process 3 Exhaust airflows should be properly set for each exhaust hood and supply or make up air should be brought into the space to balance the exhaust air leaving the s...

Страница 15: ...tion Maintenance Manual OM 006 112016 rev2 EN CROSS SECTION OF CAPTURE JET WATER WASH HOOD Item Description A Water Wash Intake Supply B Water Wash Nozzle Manifolds C Multi cyclone KSA extractor D Dra...

Страница 16: ...arsh or abrasive cleaners on Stainless Steel or Painted surfaces making sure to wipe clean all interior and exterior surfaces of the hood including the light fixtures Never clean the hood canopy when...

Страница 17: ...the nozzles in the wash manifold that washes the inside of the KSA grease filter The B5 nozzles have an inlet connection size of 1 8 orifice diameter 0 031 The balance of the nozzles which wash the in...

Страница 18: ...Wash Operation Maintenance Manual OM 006 112016 rev2 EN Control Panel Operation The Water Wash control panel is designed to operate only under safe conditions and warn when there are fan failures or o...

Страница 19: ...19 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...

Страница 20: ...cator will change text from Fan OFF to Fan ON When the exhaust fan is on pressing on the left of the virtual rocker switch will turn the exhaust fan off At the bottom of the screen is a red light that...

Страница 21: ...sired wash cycle start time using the 24 hour format for the days of the week selected The Use End Time should be set 15 seconds later than the Start Time This second setting Use End Time ensures the...

Страница 22: ...xhaust fan is turned off before the first wash cycle starts All wash cycles will complete one after the other until all hoods and or duct sumps have been washed The wash and rinse times are entered in...

Страница 23: ...ack font the alarm is an active alarm The remaining alarm history will be in green font Active alarms require action by an authorized service technician Detergent Prime Pump Screen Press and hold the...

Страница 24: ...n Maintenance Manual OM 006 112016 rev2 EN Menu Options button Pressing the Menu Options button at the bottom left of the screen will bring up a quick access screen overlay that allows the user to sel...

Страница 25: ...r Wash Operation Maintenance Manual OM 006 112016 rev2 EN Water Wash User Guide The Water Wash User Guide button will take you through depictions of all of the screens with explanations of the functio...

Страница 26: ...26 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...

Страница 27: ...Wash Operation Maintenance Manual OM 006 112016 rev2 EN Electrical Wiring Connections Two electrical wiring diagrams are shown below 1 Control Panel electrical wiring diagram 2 Field wiring diagram CO...

Страница 28: ...28 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN FIELD WIRING DIAGRAM...

Страница 29: ...p Date Product Serial Numbers Contact Information Contact Name Title Chef Kitchen Mgr Facility Mgr Property Mgr etc Facility Management Company Name if applicable Email Phone Number Cell Number Fax co...

Страница 30: ...ied third party No claims for labor charges will be approved for payment if work commences without prior authorization by Halton Purchaser shall pay incurred premium labor charge including overtime we...

Отзывы: