SENSITRON
A Halma Company
MT2276E
GALILEO 32
Manual (EN)
P. 24/14
By the options of this screen, unlike the Operator level, the “Maintenance” level
and the “Engineer” level may:
-
Put in Set or Unset the selected channel
-
Put in Test/Maintenance and take out of Test/Maintenance the select-
ed channel
-
SET / UNSET
An user with the MAINTENANCE level cannot UNSET more than 50%
of the system’s channels and relays.
The only exception is the ENGINEER level, which may UNSET the
whole system if necessary. It is required to do so for maintenance
operations in the installation where the gas detection systems is in-
stalled.
-
TEST / EXIT TEST
Will put to TEST mode or take out of the TEST (EXIT TEST) mode the
selected channel. It is possible to put in TEST mode just parts of the
system at user level “Maintenance” or “Engineer”. (See chapter 3.6.
Test/Maintenance mode for details). If more than half of the system
selected, a warning screen will pop-up.
Until the number of channels to put in Test/Maintenance mode does
not exceed the defined limits, the selected items will change the status
into TEST, as in the screen bellow:
The channel remain in TEST until the Channel Maintenance Time set
for the Galileo 32 control panel by the Configuration software (10-60
minutes) is expired.
The EXIT TEST option takes out of the Test/Maintenance mode the
selected channel.
Figure 5.1.4
d) Screen with channels in “Test”