I
ACK
Pressing 1 ACK with the cursor on the active event, will acknowledge it.
There are two situations:
-
The user is already logged in for a previous operation that requires
login. In this case pressing 1 ACK will simply refresh the screen image
and show an “X” letter on the “A” column (the “Acknowledged” column).
-
The user is not yet logged in. In this case the LOGIN dialogue window
pops up and the user should key in the password. After which the “X”
letter will be shown under the “A” column of the related active event.
Practically this is the only situation when the login of an “Operator”
level user is required so that a trace is being kept about the person
who acknowledged the active event.
II
RESET
Pressing 2 RESET with the cursor on the active event, will reset it, so
the event will disappear from the active events list. Like described abo-
ve there are two situations:
-
The user is already logged in for a previous operation that requires
ogin. In this case pressing 2 RESET will simply refresh the screen im-
age and delete the event line from the list.
-
The user is not yet logged in.
In this case the LOGIN dialogue window pops up and the user should key in the
password. After which the screen will be refreshed and the event deleted.
Note
An “Operator” level is NOT allowed to reset active events. He can only acknowl-
edge them so that the display image may be switched back to the main screen.
The reset may only be done by “Maintenance” or “Engineer” level users.
5.1.2
EVENT LOG
In the main window, at any user level, one of the options on the bottom side
menus is EVENTS LOG. Using the up/down arrow keys and then selecting the
“EVENTS LOG” option, followed by ENTER, one enters a submenu. The window
that opens will show the most recent event, in chronological order.
Figure 5.1.2
a) Event detail screen
-
Using the up/down arrow keys one may scroll through the list.
-
Using the 2 and 4 keys, one may refine the search
-
Pressing the ESCAPE key instead will switch back to the main window.
Should 3 minutes pass without any key pressed, the view switches to the Opera-
tor main window.