Figure 5.1.3
c) Relay screen options
Figure 5.1.3
d) Screen with relays in “Test” status
By the options of this screen, unlike the Operator level, the “Maintenance” level
and the “Engineer” level may:
-
Put in Set or Unset the selected relay
-
Put in Test/Maintenance and take out of Test/Maintenance the select-
ed relay
-
SET / UNSET
An user with the MAINTENANCE level cannot UNSET more than 50%
of the system’s channels and relays.
The only exception is the ENGINEER level, which may UNSET the
whole system if necessary. It is required to do so for maintenance op-
erations in the installation where the gas detection systems is installed.
-
TEST / EXIT TEST
Will put to TEST mode or take out of the TEST (EXIT TEST) mode the
selected relay. It is possible to put in TEST mode just parts of the sys-
tem at user level “Maintenance” or “Engineer”. (See chapter 3.6. Test/
Maintenance mode for details). If more than half of the system select-
ed, a warning screen will pop-up.
Until the number of relays to put in Test/Maintenance mode does not
exceed the defined limits, the selected items will change the status into
TEST, as in the screen bellow:
The relay remain in TEST until the Channel Maintenance Time set for
the Galileo8 control panel by the Configuration software (10-60 min-
utes) is expired.