3
1. Error Messages
3-5
Er
ro
r Hand
ling
95
MR400 format table setting: String code error
There is an invalid code after “\” in the string.
96
MR400 format table setting: String size error
The total size of the string is too large.
97
Multi-language font setting error
Transfer the first language font or screen
program again.
99
Registration items occupy too much memory
capacity.
Reduce the number of registration items.
100
Universal serial: GD-80 compatible entry mode
is set.
Deselect [GD-80 Compatible] from the entry
mode part.
101
Universal serial: System device memory setting
error
Check whether or not access to the outside of
the specified device memory address is
attempted, such as by macro indirect
designation.
102*
Connection mode setting error
Contact your local distributor.
103*
Network I/O size setting error
104*
Network table setting error
120
The connection port for Multi-link2 does not
match the setting for [Connect Port] in the
[Multi-link2] window.
Check the connection port setting in the
[Multi-link2] window.
121
Multi-link2 station number error. The value for
[Local Port No.] or [Total] is out of the range of 1
to 4.
The value for [Local Port No.] or [Total] in the
[Multi-link2] window is out of the range of 1 to 4.
Set [Local Port No.] or [Total] within the range of
1 to 4.
122
Multi-link program is not registered.
Transfer the multi-link program.
123
Multi-link2 program is not registered.
127
MONITOUCH does not support the remote
desktop window display.
Check whether MONITOUCH is a model that
supports the remote desktop window display. If
not, remove the setting.
130*
Ethernet: Network byte error
Contact your local distributor.
131
Ethernet: The local station number is not set in
the table.
Check the station number in Local mode, and
check that it is also set in the network table edit
window.
132
Ethernet: The connection target is not
registered or is different.
Check the settings in [PLC Table] under
[Hardware Setting]
[Target Settings].
133
Ethernet: IP address No. error
Check the IP address in the network table edit
window.
134
Ethernet: Port No. error
Check the port number setting in the network
table edit window.
135
FL-net: FL-net data error
Check the FL-net settings in the [Hardware
Setting] window.
136
IP address setting error: The network table
number selected for the local station IP address
is not registered.
Check the network table number.
137
The Ethernet port number of the I/F driver is not
unique.
Set a unique port number for the I/F driver.
138
The remote desktop table is not registered.
Register the remote desktop table with the
specified number.
139
The remote desktop table is not set correctly.
Check the remote desktop table settings again.
(Check, for example, whether an unregistered
remote desktop table number is specified.)
140
The I/F driver version of MONITOUCH does not
match the version of the MONITOUCH system
program.
Check that the MONITOUCH system program
version is compatible with the device
connected, and if necessary, update the system
program.
141*
Multi-link2 connection is set.
Contact your local distributor.
142
I/F driver not registered
Transfer the I/F driver.
Or check the device memory of the item.
Error No.
Contents
Solution
Содержание Monitouch V9 Series
Страница 1: ...Troubleshooting Maintenance Manual ...
Страница 9: ...11 Before Operation 2 Function Switches 3 System Menu 4 Status Bar MONITOUCH Operations ...
Страница 33: ...1 24 4 Status Bar Please use this page freely ...
Страница 34: ...21 Switching to Local Mode 2 Local Mode Screen 3 Handling Data Changed in Local Mode Local Mode Screen ...
Страница 94: ...2 60 3 Handling Data Changed in Local Mode Please use this page freely ...
Страница 95: ...31 Error Messages 2 Troubleshooting Error Handling ...