ERROR CODES & PROBLEM SOLVING
PAGE 52
ENGLISH
Overheat Protection for Discharge Temperature
Outdoor Display
LED1 Flashes 8 Times
Spare Parts:
Outdoor PCB
Exhaust sensor
Turn the unit on. Check the
exhaust temperature of the
compressor.
The power supply is unstable.
There is loss of refrigerant
Check refrigerant charge
The outdoor PCB is faulty, replace
the PCB
Does the temperature
exceed 230F shortly after the
compressor starts up?
Check exhaust temp sensor
resistance. Is it correct?
The sensor is faulty,
replace the sensor
No
No
No
Yes
Yes
Yes
Communication Fault Between Indoor and Outdoor Units
Indoor Display
Outdoor Display
E7
LED1 Flashes 15 Times
Spare Parts:
Indoor PCB
Outdoor PCB
Power module
Correct the wiring between the
indoor and outdoor units
1. Check that the wiring
connections are securely
fastened
2. Check whether the LN wires
are reverse connected
Check the outdoor PCB LED
No
Yes
LED
LED 1
LED 2
Solution
ON/OFF
OFF
ON
Outdoor PCB fault
ON/OFF
ON
ON
This is caused by Outdoor PCB or Indoor PCB fault. Change
one part firstly, it still unsolved, change another one.
ON/OFF
OFF
OFF
This is caused by Outdoor PCB or Power module fault.
Change one part firstly, if still unsolved change another one.
Содержание 1U09ES2VHA
Страница 2: ... This page intentionally left blank ...
Страница 6: ...INTRODUCTION PAGE 6 ENGLISH This page intentionally left blank ...
Страница 18: ...REMOTE CONTROL FUNCTIONS PAGE 18 ENGLISH This page intentionally left blank ...
Страница 34: ...SEQUENCE OF OPERATION PAGE 34 ENGLISH This page intentionally left blank ...
Страница 44: ...INSTALLATION PAGE 44 ENGLISH This page intentionally left blank This page intentionally left blank ...
Страница 58: ...REFERENCE INFORMATION PAGE 58 ENGLISH Outdoor Board Diagram ...
Страница 61: ...REFERENCE INFORMATION PAGE 61 ENGLISH Indoor Board Diagram ...
Страница 75: ... This page intentionally left blank ...