ERROR CODES & PROBLEM SOLVING
PAGE 53
ENGLISH
Loss of Synchronism Detection
Outdoor Display
LED1 Flashes 18 or 19 Times
Spare Parts:
Compressor
Power module
1. The compressor wiring is
incorrect or has bad connections
2. The compressor is damaged
Turn the unit on.
Does the compressor start?
The compressor starts, but soon stops.
LED1 on the outdoor PCB starts blinking
18/19 times at a 1Hz rate
The power module is faulty,
replace the power module
The compressor is faulty,
replace the compressor
Yes
Yes
Problem Remains
No
Indoor Unit Overload in Heating Mode
Outdoor Display
LED1 Flashes 18 or 19 Times
Spare Parts:
Indoor pipe sensor
Indoor PCB
Refrigerant
Recharge to specifications
1. The pipe sensor is faulty
2. The indoor PCB is faulty
Clean the air filter
Check the system refrigerant
charge.
Is it over or under charged?
Is the malfunction reported after the unit
has been operating for a period of time
Is the indoor air filter dirty?
No
No
Yes
Yes
Yes
Содержание 1U09ES2VHA
Страница 2: ... This page intentionally left blank ...
Страница 6: ...INTRODUCTION PAGE 6 ENGLISH This page intentionally left blank ...
Страница 18: ...REMOTE CONTROL FUNCTIONS PAGE 18 ENGLISH This page intentionally left blank ...
Страница 34: ...SEQUENCE OF OPERATION PAGE 34 ENGLISH This page intentionally left blank ...
Страница 44: ...INSTALLATION PAGE 44 ENGLISH This page intentionally left blank This page intentionally left blank ...
Страница 58: ...REFERENCE INFORMATION PAGE 58 ENGLISH Outdoor Board Diagram ...
Страница 61: ...REFERENCE INFORMATION PAGE 61 ENGLISH Indoor Board Diagram ...
Страница 75: ... This page intentionally left blank ...