TXE530
32
6LE001714A
No.
Name
Function of the object
Data type
Flags
14
Time master
Output
3 Byte - 10.001 DPT_TimeOfDay
C, R, T
This object is activated when the
Date and time
setting has the value
Master
or
Slave
.
This object sends the reference time from the weather station on the KNX bus.
Object value:
For further information, see:
.
Byte 3 (MSB)
Byte 2
Byte 1 (LSB)
Day
Hours
Minutes
Seconds
D
D
D
T
T
T
T
T
0
0
M
M
M
M
M
M
0
0
W
W
W
W
W
W
Fields
Code
Value
Units
Day
Binary
0 = any day
1 = Monday ... 7 = Sunday (3 bit)
Hours
Binary
0 to 23 (5 bit)
Hours
Minutes
Binary
0 to 59 (6 bit)
Minutes
Seconds
Binary
0 to 59 (6 bit)
Seconds
Содержание TXE530
Страница 66: ...TXE530 66 6LE001714A...