![hager TXE530 Скачать руководство пользователя страница 28](http://html2.mh-extra.com/html/hager/txe530/txe530_manual_3261705028.webp)
TXE530
28
6LE001714A
No.
Name
Function of the
object
Data type
Flags
3
Day/night
Output
1 Bit - 1.011 DPT_State
C, R, T
These objects are always activated.
This object sends the "day/night" information from the weather station on the KNX bus.
-
The "Day" information is activated (bit = 0) if the value measured is greater than the threshold value + hysteresis (12 Lux)
for more than one minute (fixed value).
-
The "Night" information is activated (bit = 1) if the value measured is less than the threshold value (10 Lux) for one
minute.
The information is sent 2 times every 24 hours (switching from day to night and night to day).
For further information, see:
No.
Name
Function of the
object
Data type
Flags
4
Wind alarm 1
Output
1 Bit - 1.005 DPT_Alarm
C, R, T
5
Wind alarm 2
Output
1 Bit - 1.005 DPT_Alarm
C, R, T
6
Wind alarm 3
Output
1 Bit - 1.005 DPT_Alarm
C, R, T
These objects are always activated.
This object sends the alarm command from the weather station on the KNX bus.
-
The wind alarm is activated (bit = 1) if the value measured is greater than the threshold value for more than 2 seconds. It
will immediately be transmitted and every 10 minutes thereafter.
-
The wind alarm is deactivated (bit = 0) if the value measured is less than the threshold value for more than 5 minutes. It
will immediately be transmitted and every 10 minutes thereafter.
Wind alarm 1: The alarm threshold is fixed at 4 m/s.
Wind alarm 2: The alarm threshold is fixed at 8 m/s.
Wind alarm 3: The alarm threshold is fixed at 12 m/s.
For further information, see:
No.
Name
Function of the
object
Data type
Flags
7
Rain alarm
Output
1 Bit - 1.005 DPT_Alarm
C, R, T
These objects are always activated.
This object sends the alarm command from the weather station on the KNX bus.
-
The rain alarm is activated (bit = 1) when rain is detected. It will immediately be transmitted and every 10 minutes
thereafter.
-
The rain alarm is deactivated (bit = 0) after a period of 5 minutes after rain has stopped. It will immediately be transmitted
and every 10 minutes thereafter.
For further information, see:
.
No.
Name
Function of the
object
Data type
Flags
8
Frost alarm
Output
1 Bit - 1.005 DPT_Alarm
C, R, T
These objects are always activated.
This object sends the alarm command from the weather station on the KNX bus.
-
The frost alarm is activated (bit = 1) if the value measured is less than the threshold value (3 °C) for 5 minutes. It will
immediately be transmitted and every 10 minutes thereafter.
-
The frost alarm is disabled (bit = 0) if the value measured is greater than 5 °C. It will immediately be transmitted and
every 10 minutes thereafter.