TXE530
10
6LE001714A
Date and time for Slave
In slave mode, the weather station synchronizes itself to the date and time of the master system. However, it always operates
with its own date and time when calculating the azimuth and elevation.
When the weather station does not receive date and time information over 2 successive tries (fixed value), it sends a request via
the object (Date and time request). If there is no response, the weather station switches automatically to master mode. When the
master device re-sends the date and time, the weather station returns to slave mode.
Date and time in Autonomous mode
The weather station operates with its own date and time to calculate the azimuth and elevation. No item is sent to or read on the
KNX bus.
Communication objects:
9 - Date slave - Input
(3 Byte - 11.001 DPT_Date)
10 - Time slave - Input
(3 Byte - 10.001 DPT_TimeOfDay)
11 - Date and time slave - Input
(8 Byte - 19.001 DPT_Date_Time)
13 - Date master - Output
(3 Byte - 11.001 DPT_Date)
14 -
Time master - Output
(3 Byte - 10.001 DPT_TimeOfDay)
15 - Date and time master - Output
(8 Byte - 19.001 DPT_Date_Time)
16 - Date and time request - Output
(1 Bit - 1.017 DPT_Trigger)
Содержание TXE530