Heat protection
Heat protection is used to prevent the room from overheating and to limit the use of the air conditioning system.
It depends on:
-
the luminosity on the facade (more than 40 klux)
-
the position of the sun on the facade
-
the outdoor temperature on all of the facades
-
or the indoor temperature on the facade 1
Heat protection operation:
If
the luminosity level is sufficient (more than 40 Klux for more than one minute)
and
the sun is shining on the facade
and
the
outdoor temperature is greater than 33 °C
or
the indoor temperature is greater than 28°C on the facade 1:
-
The heat protection is activated. The shutters and blinds close completely. This function is prioritized on the shading
control.
If
the luminosity level is insufficient (less than 40 Klux for more than 10 minutes)
or
the sun is not shining on the facade
or
the
outdoor temperature is less than 28 °C
and
the indoor temperature is less than 25°C for facade 1 for more than 15 minutes:
-
The heat protection is deactivated. The shutters and blinds remain in position.
Heat recovery
To save energy, the heat recovery system contributes to heating up the room by using the sun's energy.
It depends on:
-
the luminosity on the facade
-
the position of the sun on the facade
-
the outdoor temperature on all of the facades
-
or the indoor temperature on the facade 1
Parameter
Description
Value
Use of heat protection
automatic control
The heat protection automatic control is:
Not active
No*
Active
Yes
Parameter
Description
Value
Heat protection conditions
This setting defines the conditions so that the heat
protection is activated.
The value of this setting is fixed.
Sun on the facade
Luminosity > 40 klux
Outdoor > 33 °C or (only facade 1)
indoor > 28 °C*