background image

TE331

1

6T 8722-02a

Tebis TX100 Configurator

Consumption indicator TE331

Electrical / Mechanical characteristics: see product user's instructions

Product reference

Product designation

TX100 version

TP device      
RF device    

TE331

Consumption indicator

> 2.7.58

 

 

 

Input modules

Consumption indicator TE331

Products KNX

Display

 Tariff

 Measurement of 

electricity consumption

 Temperature 

measurement

(Only for France)

Содержание tebis TX100

Страница 1: ...acteristics see product user s instructions Product reference Product designation TX100 version TP device RF device TE331 Consumption indicator 2 7 58 Input modules Consumption indicator TE331 Product...

Страница 2: ...of the input numbering 12 6 Configuration and setting in standard mode 13 7 Tele information Setting 13 8 Configuration and setting in Expert mode 13 8 1 General points 13 8 2 Easy Prog mode 14 8 3 E...

Страница 3: ...he consumption indicator also has 2 tariff inputs Tele information and T1 T2 a temperature input for the connection of an outdoor sensor or an ambiance sensor The system can be constructed with severa...

Страница 4: ...TJA450 Clock TX022 TX023 N L1 L2 L3 TE331 CTz CTy CTx N L1 L2 L3 TE331 Ranges clock EG103x EG203x All other meters with tariff relay by dry contact 230V T1 0V T2 230V French energy meter Temperature...

Страница 5: ...The function is used to supply the consumed energy value on the bus for each metering input Partial meter Reset The function is used to reset the partial counters to zero for all the metering inputs...

Страница 6: ...arity of the toroids is of no importance 1 channel to report the data from the general meter by tele information Only for France 2 2 Description of measurement 1 Power meter 1 Total energy meter 1 Par...

Страница 7: ...easurement Meter reset KNX KNX METERING BY CALCULATION Measurement by calculation Metering is the result of a calculation between the total consumption and one or more metering channels Metering by ca...

Страница 8: ...d The metering channel CTx is referenced to the Lx phase CTy to the Ly phase and CTz to the Lz phase In the single phase version it is essential to bridge phases Ly and Lz when outputs CTy and CTz are...

Страница 9: ...rmation 2 3 Possible installations Installation type Input x Input y Input z Additional settings Electrical heating DHW boiler OR Heat pump DHW boiler Heating DHW Sockets 2 in 1 heat pump Heating DHW...

Страница 10: ...e in the meter such as the tariff option subscribed to the power subscribed to and the consumption data By connecting this interface to equipment it is possible to monitor the development of one s con...

Страница 11: ...ion channel info 4 Product installation Steps to follow Actions on TX100 Programming the product Press the key to start memorisation Automatic allocation of group addresses Go to Menu Installation man...

Страница 12: ...LED Input No Short press BP1 Metering channel 1 Input CTx LED L2 on Short press BP2 Metering channel 2 Input CTy LED L3 on Short press BP3 Metering channel 3 Input CTz LED L4 on Long press BP1 Meterin...

Страница 13: ...e parameter is deactivated the Tele information LED is off and the metering channel is stopped This chapter describes the configuration of the product during installation using another display softwar...

Страница 14: ...format by giving them the same group address 8 2 Easy Prog mode Possible link type Link description Operation of the input Input Type Temperature The Temperature object is a data item sent on the bus...

Страница 15: ...itself to the list of inputs on the left of the TX100 screen with the same number as the output Designation TX100 ETS objects designation Description OutTemp Temperature Temperature Emission Used to s...

Страница 16: ...rical energy Used to display the consumed electrical energy value in kWh Tariff indication Used to display the current tariff Dynamic restart Used to force send mode for the electrical power value to...

Страница 17: ...objects Click on See the details to display the KNX TX100 addresses Select the number of the desired input 1 then drag and drop this input into the device field 2 9 2 Importation of group addresses S...

Страница 18: ...o To to so click on the Measurements tab for the device used then on Subscription Define your subscription by clicking on Chose a subscription model Domovea has tariff models according to the country...

Страница 19: ...any Use input T1 T2 Click on choice of subscription model then on Germany Define the tariff option between Einzeltarif and Doppeltarif Other countries Use the personalised tariff Click on choice of a...

Страница 20: ...uttons are only used for configuration with the TX100 10 Operation 10 1 Installation 10 2 Meaning of the LED s Neutral Phase Lx Ly Lz Temperature CTx CTy CTz Tele info Auxiliary tariff input T1 T2 KNX...

Страница 21: ...error or error on the channel Flashing X X X Channel 1 Operating X Flashes for every 1 Wh consumed X X No bridging in single phase or no phase in three phase X Flashing at a frequency of 0 5 Hz X X Ch...

Страница 22: ...ower is restored the data is sent normally again KNX bus fault or mains KNX bus fault The consumption indicator is deemed to be out of service No data is sent When the bus connection and power supply...

Страница 23: ...TE331 23 6T 8722 02a...

Страница 24: ...eletion The device does not belong to the installation On TE331 device Press on the physical addressing push button to detect the device On the TX100 Select Install product outside of system from Rese...

Страница 25: ...TE331 25 6T 8722 02a...

Отзывы: