91
6LE007331A
For further information about the meanings of hardware triggering system alarms, refer to the
table below:
Error
code
Criticality
level
Meaning
E001
High
L1 current sensor out of service
E002
High
L2 current sensor out of service
E003
High
L3 current sensor out of service
E004
High
N current sensor out of service
E005
High
Electronic trip unit actuator out of service
E006
High
Critical error No.4
E007
High
Critical error No.3
E008
High
Critical error No.2
E009
High
Calibrator out of service
E010
High
Software internal error
E011
High
Critical error No.1
E012
High
Critical electronic trip unit temperature
ATTENTION
For further information about the meanings of the Hardware tripping system alarms, please
refer to the Maintenance manual 6LE007897A.
Thanks to the OAC output alarm contact available as an accessory and inserted at the rear
of the electronic trip unit, the Hardware tripping system alarms are linked to the HWF output
contact, located on the terminal block of the hw+ circuit breaker (See Installation manual
6LE007893A).
• Hardware
tripping system alarms
with a High criticality level requiring
immediate action
.
Anomalies causing this type of alarm may lead to the loss of the protection functions.
Therefore, these alarms are equivalent to a trip alarm and
cause the circuit breaker to
open
.
Hardware tripping system alarms are indicated by default by a flashing screen of this type:
1
Trip indicator
2
Error code
2
1
Alarm management
11.4 System alarm