90
6LE007331A
For the meanings of the different operating system alarms, refer to the table below:
Error
code
Criticality
level
Meaning
E019
High
Level 1 internal error
E020
Medium
Faulty adjustment dial
E021
Medium
High electronic trip unit temperature error
E022
Medium
Faulty electronic trip unit OK button
E023
Medium
Corrupted digital input error
E025
Medium
Electronic trip unit internal error
E027
Medium
Processor internal power supply error
E028
Medium
Internal cycle counter error
E029
Medium
ENCT external neutral current sensor error
E040
Low
Zone Selective Interlocking (ZSI) fault
E042
Low
Incompatibly between the electronic trip unit and the circuit
breaker
E043
Low
Short Time Delay and Instantaneous Protections deactivated
E100 to E999 -
Manufacturer internal errors
ATTENTION
For further information about the meaning of the operating system alarms, please refer to
the Maintenance manual 6LE007897A.