45
6LE007331A
Circuit breaker operation
5.1 Description
The RESET button
The RESET button is used to reset the circuit breaker after tripping
(see “Closing the circuit breaker after a trip operation”, page 94)
It is either:
- out, the circuit breaker has tripped,
- in, the circuit breaker is closed.
It also has two operating modes which can be adjusted using the switch on the right of the
button:
-
Auto mode
, in which it is not necessary to press the RESET button before closing the circuit
breaker after tripping.
This mode is usually used if the circuit breaker is remotely monitored, as it can be closed
without requiring a person to perform the action on-site.
-
Manual mode
, in which the RESET button must be pressed in before the next closing
operation.
In
1
6 0
0 A
=
RESET
AUTO
MANUAL
RESET
AUTO
MANUAL
Содержание hw+
Страница 1: ...User manual hw Air circuit breaker up to 1600 A RESET AUTO MANUAL In 16 0 0 A 5 8 COM...
Страница 30: ...30 6LE007331A Protection settings 4 1 Principle Action Illustration 16 Apply a seal to the window if necessary...