87
6LE007331A
Alarm management
11.2 Overload alarm
1
Overload indicator
2
Maximum current value reached
3
Overload alarm indicator
4
Phase in which the maximum current has been reached
The overload alarm is activated as soon as the current ≥ 105% of the Ir value.
In the event of an overload alarm, a screen of this type is displayed with the
indicator
flashing and the
indicator lit and steady.
Above 112.5 % of Ir, the indicator
is lit and steady.
1
2
4
3