Esento Marine 2-4 Installation, Commissioning & Operating Manual
Approved Document UI-ESENMAR-01 Issue 6.0
27
OPERATING
Test Mode is used when testing the fire alarm system. In test mode the devices in the zone(s) in test,
detectors and call points etc, can be activated and the panel will automatically reset, enabling the system
to be tested by one person. It is possible to test head removal monitoring and to test the system with or
without the sounders.
To initialise Test Mode, firstly activate the controls by entering the four
digit code. Then press and hold the Test Mode button (2) for 3 seconds.
After 3 seconds the panel will bleep and the Test Mode LED and Zone
1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is
in test selection mode. The Sounder Status LED will also be pulsing
rapidly, this indicates that the test will be
with
sounders. (Test mode
without sounders is explained below)
Pressing the Test Mode button again will move test selection mode to Zone 2 and the Zone 2 Fault/
Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 and 4.
After Zone 4 the next press will move the selection mode to the sounder circuits, indicated by no Zone
Fault/Disabled/Test LEDs on. This position selects whether or not the sounders will ring during test.
Pressing the button once more will move the selection back to Zone 1 again.
When the desired zone to be tested is indicated by a slow pulsing LED,
use the ENTER button to select it. Once selected the indicator LED will
change to a rapid pulse. Pressing ENTER again will toggle the zone
between in and out of test. Then use Test Mode button again to move to
the next zone. Any or all zones can be in test mode simultaneously.
When at the sounder status position, use the ENTER button to toggle
between testing with or without sounders. A rapid pulse = with sounders
(default), a slow pulse = without sounders.
When all zones to be tested have been set, press and hold the Test Mode button for 3 seconds again. This
will exit the test selection mode. All zones in test and the Test Mode will now be indicated by a steady LED.
To take zones out of test mode, repeat the above process using the Test Mode button to select the zone
and the ENTER button to change the status.
Test Mode With Sounders
Activation of a call point or detector - sounders will pulse twice, device is automatically reset.
Removal of a detector - sounders will pulse once.
Test Mode Without Sounders
Activation of a call point or detector - panel buzzer and LED response only, device is automatically reset.
Tip:
With the controls active, pressing the Test Mode button briefly will reveal which circuits are in test mode
(as opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time.
TEST MODE