OPERATING
Disable Mode is used to disable or isolate individual zone circuits or all sounder circuits or all auxiliary
outputs.
To initialise Disable Mode, firstly activate the controls by entering
the four digit code. Then press and hold the Disable Mode
button (1) for 3 seconds.
After 3 seconds the panel will bleep and the General Disablement
LED and Zone 1 Fault/Disabled/Test LED will pulse slowly,
indicating that Zone 1 is in disable selection mode.
Pressing the Disable Mode button again will move disable selection mode to Zone 2 and the Zone 2 Fault/
Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 and 4.
After Zone 4 the next press will move the selection mode to the sounder circuits, indicated by the Sounder
Status LED and then to the Aux outputs, indicated by the Aux Output Status LED. Pressing the button
once more will move the selection back to Zone 1 again.
When the desired circuit or output to be disabled is indicated by a slow
pulsing LED, use the ENTER button to select it. Once selected the
indicator LED will change to a rapid pulse. Pressing ENTER again will
toggle the circuit between disabled and enabled. Then use Disable Mode
button again to move to the next circuit. Any or all circuits can be disabled
simultaneously.
When all disablements have been set, press and hold the Disable Mode
button for 3 seconds again. This will exit the disable selection mode and the panel will return to standby.
All disabled circuits and the General Disablement will now be indicated by a steady LED.
To enable the circuits again, repeat the above process using the Disable Mode button to select the circuit
and the ENTER button to remove the disablement.
Tip:
With the controls active, pressing the Disable Mode button briefly will reveal which circuits are disabled (as
opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time.
DISABLE MODE
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Содержание ESEN-2MAR
Страница 44: ...www haes tech com ...