Esento Marine 2-4 Installation, Commissioning & Operating Manual
Approved Document UI-ESENMAR-01 Issue 6.0
19
SETUP & PROGRAMMING
3
1
2
1
Zone Function Settings
There are 4 functional settings available for each zone. These are as follows:
Fire latching
Normally a zone latches a fire input signal. This setting allows the panel to clear automatically when a fire
signal is removed. This is useful for interfacing purposes.
Short circuit as alarm (EN54!)
For Older non EN54 or BS5839 compliant systems. This allows a short circuit to activate a fire rather than
a fault condition.
Intrinsically safe operation
This option changes the zone alarm and short circuit thresholds to allow for an MTL 5061 type intrinsically
safe barrier to be used in the circuit.
Detector removal monitoring (EN54!)
The detector removal monitoring can be turned off. For use with older, non compliant detectors.
Enter the above code and press the ENTER button.
The zone 1 fire LED will light. This indicates setting the above attributes
for zone 1.
The amber, fault / disabled / test LEDs will show the current settings for that zone.
Use button 1 to move to the zone that requires editing.
With the required zone for editing LED lit, press the ENTER button to
enter ‘editing mode’.
The fire zone 1 LED will now pulse to indicate the editing of attribute 1 (fire latching) for the selected zone.
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Содержание ESEN-2MAR
Страница 44: ...www haes tech com ...